QUICK REFERENCE OF PARAMETERS AND FAULTS
Param.
Description
Adjustable range
Factory
setting
Page
Bypass of the cell W12
0 = Disable
1 = Mechanical bypass cell
2 = Manual activation of the bypass relay
3 = Automatic bypass after a manageable fault
4 = Automatic bypass by parallel association
0
RL8 Function MVC3
0 = Not used
1 = Output contactor drive for operation with filter type
2
2 = Output contactor drive for operation with permanent
magnet machine
0
Cells in parallel
0 = No parallelism
1 = 2 cells in parallel
2 = 3 cells in parallel
0
Transformer at the input
0 = 1 transformer
1 = 2 transformers
2 = 3 transformers
2
✓
NOTE!
Quick parameter reference notes:
(1)
Parameter can be changed only with the inverter disabled (motor stopped).
(2)
Values may change as a function of the ”Motor Parameters”.
(3)
Values may change as a function of the parameter P0412 (Lr/Rr Constant).
(4)
Values may change as a function of the parameter P0296 (Inverter rated voltage).
(5)
Values may change as a function of the parameter P0295 (Inverter rated current).
(6)
Values may change as a function of the parameter P0320 (Flying Start/Ride-Through).
(7)
Parameter can only be changed with input cubicle opened.
MVW3000 | 1-31