5
DETAILED PARAMETER DESCRIPTION
P0428 - Inductance LQ sigma
Adjustable range:
0.00 to 99.99 mH
Factory setting:
4.41 mH
Acesso:
Menu
→
Configurations
→
Nominal data
→
Motor
Description:
Motor parameter used in stator flux model.
✓
NOTE!
This parameter is only visible on the HMI when: P0950 = 1 (Synchronous motor with brushes).
This parameter is only visible on the HMI when: the control type is vector, P0202 = 3 (Sensorless
Vector) or P0202 = 4 (Vector with Encoder).
P0429 - Resistence RD
Adjustable range:
0.000 to 9.999 Ω
Factory setting:
1.139 Ω
Acesso:
Menu
→
Configurations
→
Nominal data
→
Motor
Description:
Motor parameter used in the stator flux model.
✓
NOTE!
This parameter is only visible on the HMI when: P0950 = 1 (Synchronous motor with brushes).
This parameter is only visible on the HMI when: the control type is vector, P0202 = 3 (Sensorless
Vector) or P0202 = 4 (Vector with Encoder).
P0430 - Resistance RQ
Adjustable range:
0.000 to 9.999 Ω
Factory setting:
0.831 Ω
Acesso:
Menu
→
Configurations
→
Nominal data
→
Motor
Description:
Motor parameter used in the stator flux model.
✓
NOTE!
This parameter is only visible on the HMI when: P0950 = 1 (Synchronous motor with brushes).
This parameter is only visible on the HMI when: the control type is vector, P0202 = 3 (Sensorless
Vector) or P0202 = 4 (Vector with Encoder).
P0431 - Number of motor poles
Adjustable range:
2 to 64
Factory setting:
4
Acesso:
Menu
→
Configurations
→
Nominal data
→
Motor
Description:
Number of motor poles.
MVW3000 | 5-76