DETAILED PARAMETER DESCRIPTION
✓
NOTE!
This parameter can be changed only with the motor stopped.
P0406 - Ventilation Type
Adjustable range:
0 to 1
Factory setting:
0
Acesso:
Menu
→
Configurations
→
Nominal data
→
Motor
Description:
It sets the overload protection level according to the description of parameters P0156, P0157 and P0158.
Table 5.54:
Ventilation Type
Function
0
Self-ventilated
1
Separated ventilation
✓
NOTE!
This parameter can be changed only with the motor stopped.
P0408 - Run Self-tuning
Adjustable range:
0 to 1
Factory setting:
1
Acesso:
Menu
→
Configurations
→
Nominal data
→
Motor
Description:
With P0408 = 1 (autogain) the gains of the vector control regulators are automatically recalculated when the
motor configuration parameters are changed.
Table 5.55:
Run Self-tuning
Function
0
No
1
Self Gain
✓
NOTE!
This parameter can be changed only with the motor stopped.
This parameter is only visible on the HMI when: the control type is vector, P0202 = 3 (Sensorless
Vector) or P0202 = 4 (Vector with Encoder).
P0409 - Motor stator resistance Rs
Adjustable range:
0.000 to 9.999 Ω
Factory setting:
0.000 Ω
Acesso:
Menu
→
Configurations
→
Nominal data
→
Motor
Description:
It is the value of the motor stator resistance.
MVW3000 | 5-73