5
DETAILED PARAMETER DESCRIPTION
P0248 - Analog input AI2 filter (bipolar MVC4 board)
Adjustable range:
0.0 to 16.0 s
Factory setting:
0.0 s
Acesso:
Menu
→
Configurations
→
I/O
→
Analog inputs
Description:
It sets the time constant of the RC filter of input AI2.
P0251 - AO1 Function
Adjustable range:
0 to 21
Factory setting:
2
Acesso:
Menu
→
Configurations
→
I/O
→
Analog outputs
Description:
for further details related to the function of analog outputs.
Refer to
Chapter 7 OPTIONAL ACCESSORIES AND BOARDS on page 7-1
of the User’s Manual.
For values in the factory default (P0251 = 2 and P0252 = 1.000) AO1 = 10 V when Actual Speed = Maximum
speed reference (P0134).
AO1 output may be located on the MVC4 control board (0 to 10) V or on the EBB optional board [AO1’, (0 to
20) mA/ (4 to 20) mA]. When EBB is used, the same signal is available for MVC4.
P0252 - Analog output AO1 gain (MVC4 or EBB board)
Adjustable range:
0.000 to 9.999
Factory setting:
1.000
Acesso:
Menu
→
Configurations
→
I/O
→
Analog outputs
Description:
It sets the gain of analog output AO1. For P0252 = 1.000 the output value of AO1 is set according to the
description “analog output indication scale” in P0262.
P0253 - AO2 Function
Adjustable range:
0 to 21
Factory setting:
5
Acesso:
Menu
→
Configurations
→
I/O
→
Analog outputs
Description:
For values in the factory default (P0253 = 5 and P0254 = 1.000) AO1 = 10 V when Motor Current = 1.5 x
P0295.
Refer to
Chapter 7 OPTIONAL ACCESSORIES AND BOARDS on page 7-1
of the User’s Manual.
For values in the factory default (P0253 = 5 and P0254 = 1.000) AO1 = 10 V when Motor Current = 1.5 x
P0295.
AO2 output may be located on the MVC4 control board (0 to 10) V or on the EBB optional board [AO2’, (0 to
20) mA/ (4 to 20) mA]. When EBB is used, the same signal is available for MVC4.
P0254 - Analog output AO2 gain (MVC4 or EBB board)
Adjustable range:
0.000 to 9.999
Factory setting:
1.000
Acesso:
Menu
→
Configurations
→
I/O
→
Analog outputs
Description:
It sets the gain of analog output AO2. For P0254 = 1.000 the output value of AO2 is set according to the
description “analog output indication scale” in P0262.
MVW3000 | 5-50
Содержание MVW3000 Series
Страница 2: ......
Страница 58: ...1 QUICK REFERENCE OF PARAMETERS AND FAULTS MVW3000 1 52...
Страница 62: ...2 SAFETY INSTRUCTIONS MVW3000 2 4...
Страница 192: ...6 SPECIAL FUNCTIONS MVW3000 6 4...
Страница 262: ...7 DIAGNOSTICS AND TROUBLESHOOTING MVW3000 7 70...
Страница 263: ......