DETAILED PARAMETER DESCRIPTION
Table 5.48:
Fieldbus
Function
0
Inactive
1
Profibus-DP 2 I/O
2
Profibus-DP 4 I/O
3
Profibus-DP 6 I/O
4
DeviceNet 2 I/O
5
DeviceNet 4 I/O
6
DeviceNet 6 I/O
7
Modbus-RTU 2 I/O
8
Modbus-RTU 4 I/O
9
Modbus-RTU 6 I/O
10
DeviceNet Drive Profile
11
Ethernet 2 I/O
12
Ethernet 4 I/O
13
Ethernet 6 I/O
✓
NOTE!
This parameter can be changed only with the motor stopped.
P0312 - Type of serial protocol
Adjustable range:
0 to 9
Factory setting:
7
Acesso:
Menu
→
Configurations
→
Communications
Description:
It defines the type of protocol used for serial communication.
Table 5.49:
Type of serial protocol
Function
0
Not Used
1
Modbus-RTU, 9600 bps, no parity
2
Modbus-RTU, 9600 bps, odd parity
3
Modbus-RTU, 9600 bps, even parity
4
Modbus-RTU, 19200 bps, no parity
5
Modbus-RTU, 19200 bps, odd parity
6
Modbus-RTU, 19200 bps, even parity
7
Modbus-RTU, 38400 bps, no parity
8
Modbus-RTU, 38400 bps, odd parity
9
Modbus-RTU, 38400 bps, even parity
✓
NOTE!
This parameter can be changed only with the motor stopped.
P0313 - Disabling with alarm A128, A129 and A130
Adjustable range:
0 to 5
Factory setting:
0
Acesso:
Menu
→
Configurations
→
Communications
Description:
It defines the inverter behavior when the serial communication is inactive (causing A0128), when the physical
connection with the Fieldbus network master is interrupted (causing error A0129), when the Fieldbus board is
inactive (causing error A0130) or when the communication between MVC3 and MVC4 boards is interrupted.
MVW3000 | 5-68
Содержание MVW3000 Series
Страница 2: ......
Страница 58: ...1 QUICK REFERENCE OF PARAMETERS AND FAULTS MVW3000 1 52...
Страница 62: ...2 SAFETY INSTRUCTIONS MVW3000 2 4...
Страница 192: ...6 SPECIAL FUNCTIONS MVW3000 6 4...
Страница 262: ...7 DIAGNOSTICS AND TROUBLESHOOTING MVW3000 7 70...
Страница 263: ......