DETAILED PARAMETER DESCRIPTION
P0490 - Graphic HMI LCD contrast adjustment
Adjustable range:
50 to 150
Factory setting:
110
Acesso:
Menu
→
Configurations
→
HMI
→
Settings
Description:
It adjusts the Graphic LCD contrast percentage.
P0491 - HMI commands configuration
Adjustable range:
0 to 2
Factory setting:
0
Acesso:
Menu
→
Configurations
→
HMI
→
Settings
Description:
It configures the origin of the inverter Local or Remote (LOC/REM) commands for ‘Serial’ type, so that the
Graphic HMI will be able to operate properly (the Graphic HMI commands are of the Modbus RTU serial type).
Table 5.56:
HMI commands configuration
Function
0
Inactive
1
Local HMI
2
Remote HMI
✓
NOTE!
This parameter can be changed only with the motor stopped.
P0493 - Sampling time of the online graphic
Adjustable range:
1 to 100 x 10 ms
Factory setting:
10 x 10 ms
Acesso:
Menu
→
Configurations
→
HMI
→
Graphic
Description:
It adjusts the time between the points presented in the online graphic function.
P0500 - Read-only parameter 1 selection
P0501 - Read-only parameter 2 selection
P0502 - Read-only parameter 3 selection
P0503 - Read-only parameter 4 selection
P0504 - Read-only parameter 5 selection
P0505 - Read-only parameter 6 selection
Adjustable range:
0 to 9
Factory setting:
P0500 = 2
P0501 = 0
P0502 = 0
P0503 = 0
P0504 = 0
P0505 = 0
Acesso:
Menu
→
Configurations
→
HMI
→
Main screen
MVW3000 | 5-83