5
DETAILED PARAMETER DESCRIPTION
Table 5.17:
Guided start-up routine
Parameter
Description
Motor rated voltage
Motor rated current
Motor rated speed
Motor Rated Freq
Not implanted in this software version
Not implanted in this software version
Run Self-tuning
0 = Inactive
1 = Autogain (automatic calculation of the gains of the
controllers)
Motor stator resistance Rs
Motor magnetization current (Imr)
Motor Flux Leakage Inductance
Lr/Rr Constant
Tm Time Constant
Refer to the specific description of each parameter for more details.
Parameters from P0409 to P0413 correspond to motor internal parameters, and they must be programmed
according to the motor nameplate data.
The values programmed at P0409 to P0413 must be different from zero; otherwise, the inverter will not leave
the guided start-up routine.
The configuration of this parameter must be done under the orientation of WEG technical assistance.
Table 5.18:
Control Type
Function
0
V/F 60 Hz
1
V/F 50 Hz
2
Adjustable V/F (refer to P0142 to P0146)
3
Sensorless Vector
4
Vector with Encoder
✓
NOTE!
This parameter can be changed only with the motor stopped.
P0203 - Special function selection
Adjustable range:
0 to 1
Factory setting:
0
Acesso:
Menu
→
Configurations
→
Functions
→
PID
Description:
It defines the special function selection.
For the PID regulator special function, refer to the detailed description of the related parameters (P0520 to
P0535).
When P0203 is changed to 1, P0265 is automatically changed to 15 - Manual/Automatic.
Table 5.19:
Special function selection
Function
0
None
1
PID regulator
MVW3000 | 5-31
Содержание MVW3000 Series
Страница 2: ......
Страница 58: ...1 QUICK REFERENCE OF PARAMETERS AND FAULTS MVW3000 1 52...
Страница 62: ...2 SAFETY INSTRUCTIONS MVW3000 2 4...
Страница 192: ...6 SPECIAL FUNCTIONS MVW3000 6 4...
Страница 262: ...7 DIAGNOSTICS AND TROUBLESHOOTING MVW3000 7 70...
Страница 263: ......