5
DETAILED PARAMETER DESCRIPTION
Table 5.68:
Function of the analog outputs of the MVC3 board
P0656 and
Function
Full scale
0
Phase Current V
5 V = P0295
1
Phase Current W
5 V = P0295
2
Phase Current U
5 V = P0295
3
Output Frequency
10 V = 120 Hz
4
Angle of the Fundamental Output Voltage
10 V = +180º
5
Modulation Index
5 V = 255
17
Reference of Voltage and Field Current for
Synchronous Machine
10 V = P0462 (A)
10 V = P0463 (V)
18
Position Adjustment of the Absolute
Encoder
10 V = +180°
34
Value fixe at 0 V
-
35
Value fixe at 10 V
-
36
Value fixe at -10 V
-
37
Voltage between Phase A and B
Measured on the Line ISOX Board
5 V = VAB
Rated
38
Voltage between Phase B and C
Measured on the Line ISOX Board
5 V = VBC
Rated
66
Inverter Status
-
86
Indication of A0073
0 V = without A0073
10 V = with A0073
187
Value of Analog Input AI1 MVC3
-
188
Torque Reference of the Inverter
-10 = -200 % *
10 V = +200 % *
* Torque percentage regarding the motor torque.
✓
NOTE!
For other options not described in
,contact WEG Technical Assistance.
P0659 - Analog output gain AO4 MVC3
Adjustable range:
0.000 to 9.999
Factory setting:
1.000
Acesso:
Menu
→
Configurations
→
I/O
→
Analog outputs
Description:
It sets the gain of analog output.
P0663 - Analog output offset AO1 MVC3
P0664 - Analog output offset AO2 MVC3
P0665 - Analog output offset AO3 MVC3
P0666 - Analog output offset AO4 MVC3
Adjustable range:
-32768 to 32767
Factory setting:
-90
Acesso:
Menu
→
Configurations
→
I/O
→
Analog outputs
Description:
It sets the offset of analog output.
-32768 = -100 %
32768 = 100 %
MVW3000 | 5-94