5
DETAILED PARAMETER DESCRIPTION
Table 5.33:
JOG Selection - REMOTE Situation
Function
0
Disable
1
HMI
JOG
key
2
Digital inputs DI3 to DI10 (P0265 to P0272)
3
Serial
4
Fieldbus
5
PLC
6
Graphic HMI
JOG
key
✓
NOTE!
This parameter can be changed only with the motor stopped.
P0231 - Actuation in the transition between Local and Remote for the HMIG
Adjustable range:
0 to 2
Factory setting:
0
Acesso:
Menu
→
Configurations
→
Commands
→
Local
Description:
P0231 defines the action to be taken by the inverter when the transition between LOCAL and REMOTE occurs
for the Graphic HMI.
This parameter only actuates when P0224 = 5 (Graphic HMI
|
and
O
key) or P0227 = 5 (Graphic HMI
|
and
O
key).
(*)
In case the motor stops, it occurs according to the programming of P0232 (Stop Selection).
Table 5.34:
Actuation in the transition between Local and Remote for the HMIG
Function
0
It keeps the motor state
1
It keeps the HMI state
2
It turns off the motor
P0232 - Stop Selection
Adjustable range:
0 to 1
Factory setting:
0
Acesso:
Menu
→
Configurations
→
Commands
→
Local
Description:
With the P0232 setting, it is possible to select between the stop modes (Run/Stop and General disable) for
the
O
key or for the STOP function (via DIx).
✓
NOTE!
When the “DISABLE GENERAL” stop mode is programmed, only drive the motor if it is stopped or
set the necessary time for which the inverter is disabled (COAST) in P0725 to ensure the motor stop,
or enable the Flystart function.
Table 5.35:
Stop Selection
Function
0
Run/Stop
1
General disable
MVW3000 | 5-43