5
DETAILED PARAMETER DESCRIPTION
Description:
It defines how the Motor speed reference (P0001) and Motor speed (P0002) will be presented when it runs at
synchronous speed.
To indicate the values in rpm:
Set P0208 to the synchronous speed according to
Table 5.21
.
Table 5.21:
Synchronous speed reference in rpm
Frequency
Number of motor poles
Synchronous Speed
2
3000
4
1500
6
1000
50 Hz
8
750
2
3600
4
1800
6
1200
60 Hz
8
900
The value shown can be calculated through the formulas:
=
speed
×
sync. speed
=
reference
×
sync. speed
Where:
Speed = present speed in rpm.
Sync. speed = 120 x P0403 / poles.
Poles = 120 x P0403 / P0402, it may be equal to 2, 4, 6, 8 or 10.
Reference = speed reference in rpm.
P0209 - Motor phase loss detection
Adjustable range:
0 to 1
Factory setting:
0
Acesso:
Menu
→
Configurations
→
Protections
Description:
The Motor Phase Loss Detection trips indicating F0076 when the following conditions are simultaneously
satisfied:
1. P0209 = Active.
2. Enabled inverter.
3. Speed reference higher than 3 %.
4. I
max
>
1.125
×
I
min
.
Where:
I
max
is the highest current of the three phases.
I
min
is the lowest current of the three phases.
Table 5.22:
Motor phase loss detection
Function
0
Inactive
1
Active
✓
NOTE!
This parameter can be changed only with the motor stopped.
MVW3000 | 5-33