5
DETAILED PARAMETER DESCRIPTION
P1362 - Temperature on the board of cell V1
P1363 - Temperature on the board of cell V2
P1364 - Temperature on the board of cell V3
P1365 - Temperature on the board of cell V4
P1366 - Temperature on the board of cell V5
P1367 - Temperature on the board of cell V6
P1368 - Temperature on the board of cell V7
P1369 - Temperature on the board of cell V8
P1370 - Temperature on the board of cell V9
P1371 - Temperature on the board of cell V10
P1372 - Temperature on the board of cell V11
P1373 - Temperature on the board of cell V12
Acesso:
Menu
→
Status
→
Measurements
→
Temperature
Description:
It indicates the temperature on the control board, in degrees Celsius (°C), of the respective cell.
P1374 - Temperature on the board of cell W1
P1375 - Temperature on the board of cell W2
P1376 - Temperature on the board of cell W3
P1377 - Temperature on the board of cell W4
P1378 - Temperature on the board of cell W5
P1379 - Temperature on the board of cell W6
P1380 - Temperature on the board of cell W7
P1381 - Temperature on the board of cell W8
P1382 - Temperature on the board of cell W9
P1383 - Temperature on the board of cell W10
P1384 - Temperature on the board of cell W11
P1385 - Temperature on the board of cell W12
Acesso:
Menu
→
Status
→
Measurements
→
Temperature
Description:
It indicates the temperature on the control board, in degrees Celsius (°C), of the respective cell.
P1500 - Automatic Bypass
Adjustable range:
0 to 1
Factory setting:
0
Acesso:
Menu
→
Configurations
→
Functions
→
Bypass
Description:
It defines the action to be taken by the control board upon the need to remove one of the cells from operation.
Depending on the fault type, the low voltage cells must be removed from the motor power supply circuit.
If P1500 = 0, in any cell fault situation, the entire system is locked.
If P1500 = 1, in situations that require the removal of the faulty cell, the Bypass function will automatically
rearrange the set by removing the damaged cell and putting the system back to operation.
If P1500 = 1, the Flying Start restart method is used.
If P1500 = 1, the time to close the bypass relay is half the Flying Start dead time (P0332).
The maximum number of bypassed cells after a manageable fault occurs is limited by parameter P1502.
Faults manageable by the automatic bypass function:
MVW3000 | 5-103
Содержание MVW3000 Series
Страница 2: ......
Страница 58: ...1 QUICK REFERENCE OF PARAMETERS AND FAULTS MVW3000 1 52...
Страница 62: ...2 SAFETY INSTRUCTIONS MVW3000 2 4...
Страница 192: ...6 SPECIAL FUNCTIONS MVW3000 6 4...
Страница 262: ...7 DIAGNOSTICS AND TROUBLESHOOTING MVW3000 7 70...
Страница 263: ......