The CT primary current must be smaller than 1.95 times the transformer primary rated current.
WARNING!
In case the user sets a value in P1550 that is out of the mandatory range, programming error will
occur.
✓
NOTE!
This parameter can be changed only with the motor stopped.
This parameter is only visible on the HMI when: P1893 (Transformer at the input) = 2 or 3 trans-
formers.
P1557 - Taps of transformer 2
Adjustable range:
-5.00 to 5.00 %
Factory setting:
0.00 %
Acesso:
Menu
→
Configurations
→
Nominal data
→
Inverter
Description:
It sets the modification occurred on the voltage supplied for the inverter cells.
Set it according to the input transformer tap connections.
✓
NOTE!
This parameter can be changed only with the motor stopped.
This parameter is only visible on the HMI when: P1893 (Transformer at the input) = 2 or 3 trans-
formers.
P1558 - Transformer 2 rated power
Adjustable range:
0 to 10000 kVA
Factory setting:
1500 kVA
Acesso:
Menu
→
Configurations
→
Nominal data
→
Inverter
Description:
It sets the rated power of the input transformer, in kVA.
Set it according to the nameplate data of the transformer used.
✓
NOTE!
This parameter can be changed only with the motor stopped.
This parameter is only visible on the HMI when: P1893 (Transformer at the input) = 2 or 3 trans-
formers.
P1559 - Transformer 3 CT Ratio
Adjustable range:
50 to 3000
Factory setting:
200
Acesso:
Menu
→
Configurations
→
Nominal data
→
Inverter
Description:
It sets the ratio of the current transformers used in the measurement of the inverter input current.
MVW3000 | 5-107