7
DIAGNOSTICS AND TROUBLESHOOTING
Fault/alarm
Reset
Possible causes
F0351
Number of programmed cells
exceeds the inverter capacity
Power-on.
Manual (
O
/RESET key).
Auto-reset.
It resets automatically after the cause is
eliminated.
DIx.
Networks.
The total number of cells resulting from the in-
verter configuration exceeds the communication
capacity of the control rack; such number should
be fewer than 36 cells.
Invalid inverter configuration considering the
setting of parameters:
Inverter rated volt-
age (P0296), Number of redundant cells per
phase (P1565) and Cells in parallel (P1892).
F0359
Timeout in the communication with
the thermal protection relay
Power-on.
Manual (
O
/RESET key).
Auto-reset.
DIx.
Networks.
P0315 > 0 and the cable for communication with
the thermal protection relay disconnected or de-
fective for more than 10 s.
A0360
Fault in the temperature sensor of
the thermal protection relay CH1
Power-on.
Manual (
O
/RESET key).
Auto-reset.
It resets automatically after the cause is
eliminated.
DIx.
Networks.
Temperature sensor broken wire.
PT100 accessory connectors disconnected.
Temperature channel active without a sensor
connected to the PT100 accessory.
A0361
Fault in the temperature sensor of
the thermal protection relay CH2
Power-on.
Manual (
O
/RESET key).
Auto-reset.
It resets automatically after the cause is
eliminated.
DIx.
Networks.
Temperature sensor broken wire.
PT100 accessory connectors disconnected.
Temperature channel active without a sensor
connected to the PT100 accessory.
A0362
Fault in the temperature sensor of
the thermal protection relay CH3
Power-on.
Manual (
O
/RESET key).
Auto-reset.
It resets automatically after the cause is
eliminated.
DIx.
Networks.
Temperature sensor broken wire.
PT100 accessory connectors disconnected.
Temperature channel active without a sensor
connected to the PT100 accessory.
A0363
Fault in the temperature sensor of
the thermal protection relay CH4
Power-on.
Manual (
O
/RESET key).
Auto-reset.
It resets automatically after the cause is
eliminated.
DIx.
Networks.
Temperature sensor broken wire.
PT100 accessory connectors disconnected.
Temperature channel active without a sensor
connected to the PT100 accessory.
A0364
Fault in the temperature sensor of
the thermal protection relay CH5
Power-on.
Manual (
O
/RESET key).
Auto-reset.
It resets automatically after the cause is
eliminated.
DIx.
Networks.
Temperature sensor broken wire.
PT100 accessory connectors disconnected.
Temperature channel active without a sensor
connected to the PT100 accessory.
A0365
Fault in the temperature sensor of
the thermal protection relay CH6
Power-on.
Manual (
O
/RESET key).
Auto-reset.
It resets automatically after the cause is
eliminated.
DIx.
Networks.
Temperature sensor broken wire.
PT100 accessory connectors disconnected.
Temperature channel active without a sensor
connected to the PT100 accessory.
MVW3000 | 7-9