Manual VIPA System 300S SPEED7
Chapter 4
Deployment
HB140E - CP - RE_342-1CA70 - Rev. 09/46
4-33
Index
Sub-
Index
Name
Typ
Attr.
Map. Default value Meaning
0x2002 0x00 Number
of
elements
Unsigned8
ro
N
0
Number of available
entries
0x01 1. Node-ID for
PLC-STOP
Unsigned8 rw N 0
Node-ID
(value range:1...127)
... ...
...
... ... ...
...
0x10 16. Node-ID for
PLC-STOP
Unsigned8 rw N 0
Node-ID
(value range:1...127)
At PLC-STOP
Æ
PLC-RUN transition the CAN devices listed here, were
set to state operational by the NMT command
Operational
.
Index
Sub-
index
Name
Type
Attr.
Map. Default value Meaning
0x2003 0x00 Start
address
RxPDO-Counter
Unsigned8
rw
N
0
Start address RxPDO-
Counter
For the RxPDO counter a start address in the process input image of the
PLC may be defined by this index.
There is one counter for each RxPDO. The corresponding counter is
incremented with the receipt of a PDO. During the transition 255 to 0 the
counter jumps automatically to 1. The counter is reset to 0 in the default
and in CPU STOP state.
PII address
Meaning
X
Counter for RxPDO 1
X+1
Counter for RxPDO 2
X+2
Counter for RxPDO 3
X+3
Counter for RxPDO 4
X+4
Counter for RxPDO 5
X+5
Counter for RxPDO 6
….
X+35
Counter for RxPDO 36
X+36
Counter for RxPDO 37
X+37
Counter for RxPDO 38
X+38
Counter for RxPDO 39
X+39
Counter for RxPDO 40
X+40
Counter for SYNC-Message
Node-ID - PLC-Run
Start address
RxPDO-Counter
Содержание 300S SPEED7 - CP
Страница 1: ...VIPA System 300S SPEED7 CP 342 1CA70 Manual HB140E_CP RE_342 1CA70 Rev 09 46 November 2009...
Страница 4: ...Contents Manual VIPA System 300S SPEED7 ii HB140E CP RE_342 1CA70 Rev 09 46...
Страница 8: ...Safety information Manual VIPA System 300S SPEED7 4 HB140E CP RE_342 1CA70 Rev 09 46...
Страница 92: ...Chapter 4 Deployment Manual VIPA System 300S SPEED7 4 54 HB140E CP RE_342 1CA70 Rev 09 46...
Страница 94: ...Index Manual VIPA System 300S SPEED7 A 2 HB140E CP RE_342 1CA70 Rev 09 46 M Stich...