Chapter 4 Deployment
Manual VIPA System 300S SPEED7
4-46
HB140E - CP - RE_342-1CA70 - Rev. 09/46
Bit Name
Description
0
DiagStationNonExistent 1 = Station does not exist
0 = Station does exist
(if a boot-up messages was received or
node guarding was activated, the bit is
set to 0.)
1
DiagStationNotReady
1 = Station is in pre-operational state
0 = Station is in operational state
2 -
reserved
3
DiagExtDiag
0 = Station only has CAN diagnostics
1 = Station has external diagnostics data
7...4 -
reserved
Bit Name
Description
0
DiagPrmReq
0 = Station is successfully configured
1 =
Station should be configured once more
1 -
reserved
2 -
fix
1
3
DiagWD_ON
0 = Node Guarding is not supported
1 = Node Guarding is activated
7...4 -
reserved
The byte is reserved for future extensions.
ID of the station the diagnostics come from.
Type of station the diagnostics come from.
0 = Slave
1 = NMT master
Byte
Name
Description
0
Header
fix 29
1 Type
fix
81hex
2 SlotNr
fix
0
3
Specifier
Characteristic of the status message
0 = no further differentiation
1 = Status message appears
2 = Status message disappears
4..7
VendorID
CANopen Index 1018 SubIndex 1
8..11
ProductCode
CANopen Index 1018 SubIndex 2
12..15 RevisionNr
CANopen Index 1018 SubIndex 3
16..19 SerialNr
CANopen Index 1018 SubIndex 4
20
DiagError
Diagnostics error code (10h ... 31h)
10h = DIAG_SLAVEBOOTUP
11h = DIAG_SLAVEGRDERROR
12h = DIAG_SLAVESDOERROR
13h = DIAG_SLAVEEMCYIND
21..28 DiagErrorData
Additional data to diagnostics error
Station state 1
Station state 2
Station state 3
Node-ID
Device type
Status message
Содержание 300S SPEED7 - CP
Страница 1: ...VIPA System 300S SPEED7 CP 342 1CA70 Manual HB140E_CP RE_342 1CA70 Rev 09 46 November 2009...
Страница 4: ...Contents Manual VIPA System 300S SPEED7 ii HB140E CP RE_342 1CA70 Rev 09 46...
Страница 8: ...Safety information Manual VIPA System 300S SPEED7 4 HB140E CP RE_342 1CA70 Rev 09 46...
Страница 92: ...Chapter 4 Deployment Manual VIPA System 300S SPEED7 4 54 HB140E CP RE_342 1CA70 Rev 09 46...
Страница 94: ...Index Manual VIPA System 300S SPEED7 A 2 HB140E CP RE_342 1CA70 Rev 09 46 M Stich...