Project engineering
The project engineering of the CANopen master happens in WinCoCT
(
Win
dows
C
AN
o
pen
C
onfiguration
T
ool) from VIPA. You export your
project from WinCoCT as wld-file. This wld-file can then be imported into
the hardware configurator from Siemens.
To connect a CAN master module to your SPEED7-CPU, you have to
configure the CAN master module as VIPA_SPEEDBUS DP slave from the
SPEED-Bus hardware catalog at a virtual DP master.
For the deployment of System 300S modules and the CAN master at
SPEED-Bus, you have to include the System 300S modules into the
hardware catalog via the GSD-file from VIPA. For the project engineering
in the hardware configurator you have to execute the following steps:
•
Start WinCoCT and project the CANopen network.
•
Create a master group with
and insert a SPEED-Bus CANopen
master via
. Please consider that the Node-ID may not be changed
later.
•
Activate the master functionality by
Node
>
CANopen Manager
with
"Device is NMT Master" and confirm your setting by [Close].
•
Set parameters like diagnostics behavior and CPU address ranges with
Node
>
PLC Parameters
".
•
Create a slave group with
and add your CANopen slaves via
.
•
Add modules to your slaves via "Modules" and parameterize them if
needed.
•
Set your process data connections in the matrix via "Connections" and
proof your entries if needed in the process image of the master.
•
Save the project and export it as wld-file by
File
>
Export
.
•
Switch to the SIMATIC manager from Siemens and copy the data block
from the CAN-wld-file into the block directory.
•
Start hardware configurator from Siemens and include
SPEEDBUS.GSD for SPEED7 from VIPA.
•
Project engineering of CPU 318-2DP (6ES7 318-2AJ00-0AB0/V3.0)
from Siemens.
•
Starting with slot 4, place the System 300 modules in the plugged
sequence.
•
For the SPEED-Bus you always include, connect and parameterize to
the
operating mode
DP master the DP master CP 342-5 (342-5DA02
V5.0) as last module. To this master system you assign every SPEED-
Bus module as VIPA_SPEEDBUS slave. Here the Profibus address
corresponds to the slot no. Beginning with 100 for the CPU. Place on
slot 0 of every slave the assigned module and alter the parameters if
needed.
Overview
Fast introduction
Содержание 300S SPEED7 - CP
Страница 1: ...VIPA System 300S SPEED7 CP 342 1CA70 Manual HB140E_CP RE_342 1CA70 Rev 09 46 November 2009...
Страница 4: ...Contents Manual VIPA System 300S SPEED7 ii HB140E CP RE_342 1CA70 Rev 09 46...
Страница 8: ...Safety information Manual VIPA System 300S SPEED7 4 HB140E CP RE_342 1CA70 Rev 09 46...
Страница 92: ...Chapter 4 Deployment Manual VIPA System 300S SPEED7 4 54 HB140E CP RE_342 1CA70 Rev 09 46...
Страница 94: ...Index Manual VIPA System 300S SPEED7 A 2 HB140E CP RE_342 1CA70 Rev 09 46 M Stich...