Manual VIPA System 300S SPEED7
Chapter 4
Deployment
HB140E - CP - RE_342-1CA70 - Rev. 09/46
4-9
Activate
: Activates the Manufacturer Specific Interrupt OB 57.
Number of Messages
: Number of messages to be received to release the
OB 57.
Additionally the index 2000h in the CANopen directory must be initialized.
The following text describes the approach of the project engineering with
an abstract sample:
The project engineering is divided into four parts:
•
CAN master project engineering in WinCoCT and export as wld-file
•
Import CAN master project engineering
•
Project engineering of the modules at the standard bus
•
Project engineering of all SPEED-Bus modules as a virtual Profibus net
(you need SPEEDBUS.GSD).
Standard bus (serial)
SPEED-Bus (parallel)
CPU 31xS
DI
DO
CAN-Master
DI
DO
DIO
AI
AO
AI
DIO
For the project engineering of a CANopen system, the most recent EDS-
file has to be transferred into the EDS-directory of WinCoCT.
For the deployment of the System 300S modules, you have to include the
System 300S modules with the GSD-file SPEEDBUS.GSD from VIPA into
the hardware catalog.
Manufacturer
Specific Interrupt
(OB 57)
Steps of the
project
engineering
Hardware
Preconditions
Содержание 300S SPEED7 - CP
Страница 1: ...VIPA System 300S SPEED7 CP 342 1CA70 Manual HB140E_CP RE_342 1CA70 Rev 09 46 November 2009...
Страница 4: ...Contents Manual VIPA System 300S SPEED7 ii HB140E CP RE_342 1CA70 Rev 09 46...
Страница 8: ...Safety information Manual VIPA System 300S SPEED7 4 HB140E CP RE_342 1CA70 Rev 09 46...
Страница 92: ...Chapter 4 Deployment Manual VIPA System 300S SPEED7 4 54 HB140E CP RE_342 1CA70 Rev 09 46...
Страница 94: ...Index Manual VIPA System 300S SPEED7 A 2 HB140E CP RE_342 1CA70 Rev 09 46 M Stich...