Manual VIPA System 300S SPEED7
Chapter 4
Deployment
HB140E - CP - RE_342-1CA70 - Rev. 09/46
4-25
Index
Sub-
index
Name
Type
Attr.
Map. Default value Meaning
0x1006 0
Communi-
cation
cycle period
Unsigned32 rw
N
0x00000000
Maximum length of the
SYNC interval in µs.
If a value other than zero is entered here, the master goes into error state if
no SYNC telegram is received within the set time during synchronous PDO
operation.
Index
Sub-
index
Name
Type
Attr.
Map. Default value Meaning
0x1007 0
Synchronous
window
length
Unsigned32 rw
N
0x00000000
Contains the length of time
window for synchronous
PDOs in µs.
Index
Sub-
index
Name
Type
Attr.
Map. Default value Meaning
0x1008 0
Manufacturer
device name
Visible string ro
N
Device name of the bus
coupler
VIPA IM 342-1CA70 = VIPA CANopen Master/Slave 342-1CA70
Since the returned value is longer than 4byte, the segmented SDO protocol
is used for transmission.
Index
Sub-
index
Name
Type
Attr.
Map. Default value Meaning
0x1009 0
Manufacturer
Hardware
version
Visible string ro
N
1.00
Hardware version number of
bus coupler
VIPA 342-1CA70 = 1.00
Since the returned value is longer than 4byte, the segmented SDO protocol
is used for transmission.
SYNC interval
Synchronous
Window Length
Device name
Hardware version
Содержание 300S SPEED7 - CP
Страница 1: ...VIPA System 300S SPEED7 CP 342 1CA70 Manual HB140E_CP RE_342 1CA70 Rev 09 46 November 2009...
Страница 4: ...Contents Manual VIPA System 300S SPEED7 ii HB140E CP RE_342 1CA70 Rev 09 46...
Страница 8: ...Safety information Manual VIPA System 300S SPEED7 4 HB140E CP RE_342 1CA70 Rev 09 46...
Страница 92: ...Chapter 4 Deployment Manual VIPA System 300S SPEED7 4 54 HB140E CP RE_342 1CA70 Rev 09 46...
Страница 94: ...Index Manual VIPA System 300S SPEED7 A 2 HB140E CP RE_342 1CA70 Rev 09 46 M Stich...