Chapter 1 Basics
Manual VIPA System 300S SPEED7
1-8
HB140E - CP - RE_342-1CA70 - Rev. 09/46
The project engineering of the SPEED7-CPU has the following
components:
To be compatible with the Siemens SIMATIC manager, the following steps
are required:
Standard bus
Slot
1
2
X2
X1
3
Module
CPU 318-2
DP
MPI/DP
342-5DA02 V5.0
virtual DP master for CPU
and all SPEED-Bus modules
real modules
at the standard bus
CPs res. DP master
at the SPEED-Bus as
343-1EX11 res. 342-5DA02
343-1EX11 (internal PG/OP)
343-1EX11 (internal CP343)
(100) VIPA
VIPA_SPEEDBUS
Order number
CPU at Slot 100
SPEEDbus
Slot
0
(n) VIPA
VIPA_SPEEDBUS
Order number
Module at slot n
SPEEDbus
Slot
0
...
•
Preparation
Start the hardware configurator from Siemens and include
the speedbus.gsd for the SPEED-Bus from VIPA.
•
Project engineering of the CPU
Project a CPU 318-2DP (318-2AJ00-0AB00 V3.0). If your
SPEED7-CPU contains a DP master, you may now connect it
with Profibus and configure your DP slaves.
•
Project engineering of the real plugged modules at the
standard bus
Set the modules that are at the right side of the CPU at the
standard bus starting with slot 4.
•
Project engineering of the integrated CPs
For the internal Ethernet PG/OP channel you have to set a
CP 343-1 (343-1EX11) as 1. module at the real plugged
modules. If your SPEED7-CPU has additionally an integrated
CP 343, this is also configured as CP 343-1 but always below
the former placed CP 343-1.
•
Project engineering of the SPEED-Bus-CPs and -DP master
Plug and connect all CPs as 343-1EX11 and DP master as
342-5DA02 V5.0 at the SPEED-Bus below the former
configured internal CPU components.
Please regard that the sequence within a function group (CP
res. DP master) corresponds the sequence at the SPEED-
Bus from right to left.
•
Project engineering of the CPU and all SPEED-Bus modules
in a virtual master system
The slot assignment of the SPEED-Bus modules and the
parameterization of the in-/output periphery happens via a
virtual Profibus DP master system. For this, place a DP
master (342-5DA02 V5.0) with master system as last
module. The Profibus address must be <100!
Now include the slave "vipa_speedbus" for the CPU and
every module at the SPEED-Bus. After the installation of the
speedbus.gsd you may find this under Profibus-DP /
Additional field devices / I/O / VIPA_SPEEDbus. Set the slot
number of the module (100...110) as Profibus address and
plug the according module at slot 0 of the slave system.
To extend the bus you may use the IM 360 from Siemens, where 3 further
extensions racks can be connected via the IM 361. Bus extensions must be
placed at slot 3.
More detailed information is to be found in the chapter "Deployment CPU
31xS" at "Addressing".
Approach
Bus extension with
IM 360 and IM 361
Содержание 300S SPEED7 - CP
Страница 1: ...VIPA System 300S SPEED7 CP 342 1CA70 Manual HB140E_CP RE_342 1CA70 Rev 09 46 November 2009...
Страница 4: ...Contents Manual VIPA System 300S SPEED7 ii HB140E CP RE_342 1CA70 Rev 09 46...
Страница 8: ...Safety information Manual VIPA System 300S SPEED7 4 HB140E CP RE_342 1CA70 Rev 09 46...
Страница 92: ...Chapter 4 Deployment Manual VIPA System 300S SPEED7 4 54 HB140E CP RE_342 1CA70 Rev 09 46...
Страница 94: ...Index Manual VIPA System 300S SPEED7 A 2 HB140E CP RE_342 1CA70 Rev 09 46 M Stich...