Manual VIPA System 300S SPEED7
Chapter 2
Assembly and installation guidelines
HB140E - CP - RE_342-1CA70 - Rev. 09/46
2-5
Assembly SPEED-Bus
For the deployment of SPEED-Bus modules, a pre-manufactured SPEED-
Bus rail is required. This is available mounted on a profile rail with 2, 6 or
10 extension plug-in locations.
SLOT1
DCDC
CPU
SLOT2
SLOT3
SLOT4
SLOT5
SLOT6
SLOT1
DCDC
CPU
SLOT2
65mm
40mm
SLOT1
DCDC
CPU
SLOT2
•
Bolt the profile rail with the background (screw
size: M6), so that you still have minimum 65mm
space above and 40mm below the profile rail.
•
Please look for a low-impedance connection
between profile rail and background
•
Connect the profile rail with the protected earth
conductor.
The minimum cross-section of the cable to the
protected earth conductor has to be 10mm
2
.
Order number
SPEED-
Bus slots
A B
C
VIPA 390-1AB60
-
160mm 140mm 10mm
VIPA 390-1AE80
-
482mm 466mm 8,3mm
VIPA 390-1AF30
-
530mm 500mm 15mm
VIPA 390-1AJ30
-
830mm 800mm 15mm
VIPA 390-9BC00*
-
2000mm
-
15mm
VIPA 391-1AF10
2
530mm 500mm 15mm
VIPA 391-1AF30
6
530mm 500mm 15mm
VIPA 391-1AF50
10
530mm 500mm 15mm
G
122
* Unit pack 10 pieces
Pre-manufactured
SPEED-Bus
profile rail
Installation of the
profile rail
Profile rail
Содержание 300S SPEED7 - CP
Страница 1: ...VIPA System 300S SPEED7 CP 342 1CA70 Manual HB140E_CP RE_342 1CA70 Rev 09 46 November 2009...
Страница 4: ...Contents Manual VIPA System 300S SPEED7 ii HB140E CP RE_342 1CA70 Rev 09 46...
Страница 8: ...Safety information Manual VIPA System 300S SPEED7 4 HB140E CP RE_342 1CA70 Rev 09 46...
Страница 92: ...Chapter 4 Deployment Manual VIPA System 300S SPEED7 4 54 HB140E CP RE_342 1CA70 Rev 09 46...
Страница 94: ...Index Manual VIPA System 300S SPEED7 A 2 HB140E CP RE_342 1CA70 Rev 09 46 M Stich...