Technical data
Electrical data
VIPA 342-1CA70
Power supply
via backplane bus
Current consumption
max. 550mA
Isolation
≥
AC 500V
Status indicator
by means of LEDs located on the front
Connectors/interfaces
9pin D-type plug
CANopen connection
CAN-Bus interface
Connection
9pin D-type plug
Network topology
Linear bus, active bus termination at both ends
Medium
Screened three-core cable, unscreened cable permitted -
depending on environment.
Data transfer rate
10kBaud to 1MBaud
Max. overall length
1000m at 50kBaud without repeaters
Max. no. of stations
126 stations
Combination with peripheral
modules
Max. number of slaves
125
Max. number of TxPDOs
40
Max. number of RxPDOs
40
Max. number of input bytes
384
Max. number of output bytes
384
Dimensions and weight
Dimensions (WxHxD) in mm
40x125x120
Weight 110g