Manual VIPA System 300S SPEED7
Chapter 4
Deployment
HB140E - CP - RE_342-1CA70 - Rev. 09/46
4-49
Additional data: Emergency telegram
To send internal device failures to other participants at the CAN-Bus with a
high priority, the VIPA CAN-Bus coupler supports the Emergency Object.
It is provided with a high priority and supplies valuable information about
the state of the device and the net.
The emergency telegram has always a length of 8Byte. It starts with the
2byte error code, then the 1byte error register and finally the additional
code with a length of 5byte.
Error code
ErrorRegister Index 0x1001 Info 0 Info 1 Info 2 Info 3 Info 4
Low
Byte High
Byte
Error Code
Description
Info 0
Info 1
Info 2
Info 3
Info4
0x0000 Reset
Emergency
0x00 0x00 0x00 0x00 0x00
0x1000 PDO
Control
0xFF 0x10 PDO
Number
LowByte
Timer
Value
HighByte
Timer Value
0x6200 PLC-STOP
1=PLC-
STOP
0x00 0x00 0x00 0x00
0x6363 PDO-Mapping
Low-Byte:
Mapping
parameter
High-Byte:
Mapping
parameter
Mapping
entries
0x00 0x00
0x8100
Heartbeat Consumer
Node ID
LowByte
Timer
Value
HighByte
Timer
Value
0x00 0x00
0x8100
SDO Block Transfer
0xF1
LowByte
Index
HighByte
Index
SubIndex 0x00
0x8130
Node Guarding Error
LowByte
GuardTime
HighByte
GuardTime
LifeTime 0x00
0x00
0x8210
PDO not processed
due to length error
PDO
Number
Wrong
length
PDO
length
0x00 0x00
0x8220
PDO length exceeded PDO
Number
Wrong
length
PDO
length
0x00 0x00
DIAG_SLAVE
EMCYIND (13h)
Telegram structure
Содержание 300S SPEED7 - CP
Страница 1: ...VIPA System 300S SPEED7 CP 342 1CA70 Manual HB140E_CP RE_342 1CA70 Rev 09 46 November 2009...
Страница 4: ...Contents Manual VIPA System 300S SPEED7 ii HB140E CP RE_342 1CA70 Rev 09 46...
Страница 8: ...Safety information Manual VIPA System 300S SPEED7 4 HB140E CP RE_342 1CA70 Rev 09 46...
Страница 92: ...Chapter 4 Deployment Manual VIPA System 300S SPEED7 4 54 HB140E CP RE_342 1CA70 Rev 09 46...
Страница 94: ...Index Manual VIPA System 300S SPEED7 A 2 HB140E CP RE_342 1CA70 Rev 09 46 M Stich...