VD560 Series Inverter User Manual Communication Protocol
- 209 -
101AH
Current power on time
101BH
current running time
101CH
PULSE input pulse frequency, unit 1Hz
101DH
Communication set value
101EH
Actural feedback speed
101FH
Main frequency X display
1020H
Auxiliary frequency Y display
Note:
Communication value is relative percentage, 10000 corresponds to 100.00% and - 10000-100.00%.
The frequency of dimensional data, the percentage is relatively maximum frequency percentage
(F0-10); counter rotating torque dimensional data, the percentage is F2-10, the A3-10 (torque limit
digital set, corresponding to the first and second motor).
Control command input to the inverter: (only write)
Command address
Command function
0001: Forward rotation
0002: Reverse rotation
0003: Forward jog
0004: Reverse jog
0005: Coast to stop
0006: Decelerate to stop
0007: Fault reset
2000H
0008: Emergency stop
Read inverter state: (only read)
State Address
State Function
0001: Forward rotation
0002: Reverse rotation
3000H
0003: Stop
Parameters lock password check: (if return for 8888 h, it indicates that the password through check)
Code Address
Input code content
1F00H
*****
Digital output terminal control: (only write)
Command Address
Command Content
2001H
BIT0: DO1 output control
BIT1: DO2 output control
BIT2: RELAY1 output control
BIT3: RELAY2 output control
BIT4: FMR output control(HDO)
BIT5: VDO1
BIT6: VDO2
BIT7: VDO3
BIT8: VDO4
BIT9: VDO5
Analog output AO1 control: (only write)
Command Address
Command Content
2002H
0
~
7FFF indicate 0
%~
100
%
Analog output AO2 control: (only write)
Command Address
Command Content
2002H
0
~
7FFF indicate 0
%~
100
%
Pulse output control: (only write)