Function Parameter Table VD560 Series Inverter User Manual
- 82 -
A0-11
Low Frequency
Torque
Compensation
Amount
0.0%~50.0%
0.0%
○
A0-12
Low Frequency
Torque
Compensation
Frequency
Upper Limit
0.00Hz~Max frequency
10.00Hz
○
A0-13
High Frequency
Torque
Compensation
Amount
0.0%~50.0%
3.0%
○
A0-14
High Frequency
Torque
Compensation
Frequency
Upper Limit
0.00Hz~Max frequency
25.00Hz
○
A0-15
Rotational
Inertia
Compensation
Reference
0: Internal frequency
1: Feedforward frequency variation
2: Feedforward frequency
1
◎
A0-16
Feedforward
Frequency
Source
Selection
0: AI1
1: AI2
2: AI3 (expansion card)
3: PULSE
4: Communication setting
0
◎
A0-17
Rotational
Inertia
Compensation
Coefficient
0.00~10.00
0.00
○
A0-18
Rotational
Inertia
Compensation
Upper Limit
0.0%~50.0%
5.0%
○
A0-19
Rotational
Inertia
Compensation
Starting
Frequency
0.00Hz~max frequency
10.00Hz
○
A1 Optimize Control Parameter
Function
Code
Parameter
Name
Setting Range
Factory
Default
Value
Property
A1-00
Carrier
Frequency
0.5kHz~16.0kHz
Model
dependent
○