VD560 Series Inverter User Manual Parameter Description
- 101 -
2)
When the auxiliary frequency source for analog input given (AI1, AI2) or pulse input given, input
100% of the set corresponding auxiliary frequency source range, can be set through by the
F0-06 and F0-07.
3)
When frequency source for pulse input given, is similar to analog given.
Tip: auxiliary frequency source selection B and main frequency source A selection, can’t be set to the
same channel, namely F0-02 and F0-04 can’t set to the same value, otherwise easy to cause
confusion.
F0-05
Frequency Source
Superposition
Selection
Unit’s digit: frequency source selection
0: Main frequency source A
1: Main auxiliary operation result(operational
relationship is determined by ten Bits)
2: Main frequency source A switching with
auxiliary frequency source B
3: Main frequency source A switching with
main auxiliary operation result
Ten’s digit: frequency source main auxiliary
operation relationship
0: Main + auxiliary
1: Main – auxiliary
2: Max value of the two
3: Min value of the two
0x00
○
Through this parameter selection frequency given channel. Through the compound of main frequency
source A and auxiliary frequency source B to achieve frequency given.
Unit’s digit: frequency source selection
0: main frequency source A
Main frequency A as the target frequency.
1: main and auxiliary operation result
Main and auxiliary operation result as the target frequency, the main and auxiliary operation
relationship please see the “ten’s digit” instruction of this function code.
2: the main frequency source A switch auxiliary frequency source B
When multi-function input terminal function 20 (frequency source switch) is invalid, main frequency A
as the target frequency.
When multi-function input terminal function 20 (frequency source switch) is valid, auxiliary frequency
B as the target frequency.
3: the main frequency source A switch main and auxiliary operation result
When multi-function input terminal function 20 (frequency source switch) is invalid, main frequency A
as the target frequency.
When multi-function input terminal function 20 (frequency source switch) is valid, main and auxiliary
operation result as the target frequency.
4: auxiliary frequency source B switch main and auxiliary operation result
When multi-function input terminal function 20 (frequency source switch) is invalid, auxiliary
frequency B as the target frequency.
When multi-function input terminal function 20 (frequency source switch) is valid, main and auxiliary
operation result as the target frequency.
Ten’s digit: frequency source main and auxiliary operation relations
0: main frequency source A + auxiliary frequency source B
The sum of main frequency A and auxiliary frequency B as the target frequency. To realize frequency