Parameter Description VD560 Series Inverter User Manual
- 164 -
Fb-34
Accumulative Power-on
time Reached
0h~65535h
0h
○
Used to set the inverter power on time.
When the accumulative power on time (FF-15) reached the setting accumulative power on time,
frequency converter multi-function digital DO output ON signal.
Fb-35
Accumulative Running
Time Reached
0h~65535h
0h
○
Used to set the inverter running time.
When the accumulative running time (FF-14) reached the setting accumulative running time, inverter
multi-function digital DO output ON signal.
Fb-36
Timing Function
Selection
0: Disabled
1: Enabled
0
○
Fb-37
Timing Run Time
Selection
0: Fb-38 setting
1: AI1
2: AI2
3: AI3 (expansion card)
Analog input range corresponding to the
Fb-38
0
○
Fb-38
Timing Run Function
0.0Min~65000.0Min
0.0Min
○
This group of parameters used to complete the timing run function of the inverter.
When Fb-36 timing function selection is effective, the inverter timing starts when it is started, to set
timing run time, the inverter automatically stop, muti-function DO output ON signal at the same time.
Frequency converter starting at each time, timing starts from 0, timing remaining run time can be
viewed by U0-35.
Timing run time set by Fb-37, Fb-38, unit of time for minutes.
Fb-39
Module Temperature
Reached
0°C~100°C
75°C
○
Inverter radiator temperature reached the temperature, the inverter multi-function DO output "module
temperature reached" ON signal.
Fb-40
Lower Limit of AI1 Input
Voltage Protection Value
0.00V~Fb-41
3.10V
○
Fb-41
Upper Limit of AI1 Input
Voltage Protection Value
Fb-40~10.00V
6.80V
○
When the analog input AI1 value is less than Fb - 40, or the AI1 input is greater than Fb-41, the
inverter muti-function the DO output "AI1 input limit exceed" ON signal, for indicating whether the
input voltage of AI1 in the setting range.
Fb-42
Wakeup Frequency
Dormancy frequency (Fb-44)~max
frequency (F0-10)
0.00Hz
○
Fb-43
Wakeup Delay Time
0.0s~6500.0s
0.0s
○
Fb-44
Dormancy Frequency
0.00Hz~wakeup frequency (Fb-42)
0.00Hz
○
Fb-45
Dormancy Delay Time
0.0s~6500.0s
0.0s
○
Содержание VD560 Series
Страница 2: ......
Страница 9: ...VD560 Series Inverter User Manual Safety and Precautions 5 damage or performance reduce...