VD560 Series Inverter User Manual Parameter Description
- 157 -
with according to the selected fault processing method.
FA-28
PID Feedback Lost
Detection Starting
Frequency
0.00Hz~max frequency
10.00Hz
○
FA-29
PID Stop Operation
0: No operation when stop
1: Operation when stop
0
○
Used to select the PID in stop condition, PID whether to continue operations. General application in
the case of PID should stop operation under the stop condition.
FA-30
The Lower Limit Value of
Feedback when PID
Action
0.0%: No limit
0.1%~100.0%
0.0.%
○
When the PID feedback value is less than the lower limit, the PID regulation does not act, which is
mainly used to reduce PID regulation and maintain the stability of the system.
Содержание VD560 Series
Страница 2: ......
Страница 9: ...VD560 Series Inverter User Manual Safety and Precautions 5 damage or performance reduce...