Parameter Description VD560 Series Inverter User Manual
- 186 -
b1 Virtual IO Parameter Group
b1-00
Virtual VDI1 Terminal
Function Selection
0~59
0
◎
b1-01
Virtual VDI2 Terminal
Function Selection
0~59
0
◎
b1-02
Virtual VDI3 Terminal
Function Selection
0~59
0
◎
b1-03
Virtual VDI4 Terminal
Function Selection
0~59
0
◎
b1-04
Virtual VDI5 Terminal
Function Selection
0~59
0
◎
Virtual VDI1~VDI5 are exactly the same when the control panel DI on the function, can be used as a
multi-function digital quantity input, the detail setting please refer to the introduce of F5-00~F5-09.
b1-05
Virtual VDI Terminal
State Setting Mode
Unit’s digit: virtual VDI1
0: By virtual VDOx state to decide VDI
is valid or not
1: By code b1-06 setting VDI is valid or
not
Ten’s digit: virtual VDI2, same as
above
Hundred’s digit: virtual VDI3, same as
above
Thousand’s digit: virtual VDI4, same
as above
Ten thousand’s digit: virtual VDI5,
same as above
0x00000
◎
b1-06
Virtual VDI Terminal
state setting
Unit’s digit: virtual VDI1
0: Disabled
1: Enabled
Ten’s digit: virtual VDI2, same as
above
Hundred’s digit: virtual VDI3, same as
above
Thousand’s digit: virtual VDI4, same
as above
Ten thousand’s digit: virtual VDI5,
same as above
0x00000
◎
Different from ordinary digital quantity input terminals, the state of the virtual VDI can set two ways,
and selection by b1-05.
When selecting VDI status is decided by the state of the corresponding virtual VDO, VDI whether is
valid state, depending on the VDO output as valid or invalid, and the VDIx only binding VDOx (x is 1~
5).
When selection VDI status are setting by the function code, through the binary system of function
code b1-06, determine the status of the virtual input terminals respectively.
The following illustrates the use method of virtual VDI.
Example 1: when selecting VDO state decided to VDI, to complete the following functions: “AI1 input
Содержание VD560 Series
Страница 2: ......
Страница 9: ...VD560 Series Inverter User Manual Safety and Precautions 5 damage or performance reduce...