Parameter Description VD560 Series Inverter User Manual
- 170 -
Fig 6-33 Multistage speed operation schematic diagram
Schedule 2 is function instruction of multi-reference.
Four multi-reference terminals, can be combined into16 kinds of state, these 16 states corresponding
to16 instruction set value. As shown in table 1.
K4
K3
K2
K1
Reference Setting
Corresponding Parameter
OFF
OFF
OFF
OFF
Multi-reference 0
FC-00
OFF
OFF
OFF
ON
Multi-reference 1
FC-01
OFF
OFF
ON
OFF
Multi-reference 2
FC-02
OFF
OFF
ON
ON
Multi-reference 3
FC-03
OFF
ON
OFF
OFF
Multi-reference 4
FC-04
OFF
ON
OFF
ON
Multi-reference 5
FC-05
OFF
ON
ON
OFF
Multi-reference 6
FC-06
OFF
ON
ON
ON
Multi-reference 7
FC-07
ON
OFF
OFF
OFF
Multi-reference 8
FC-08
ON
OFF
OFF
ON
Multi-reference 9
FC-09
ON
OFF
ON
OFF
Multi-reference 10
FC-10
ON
OFF
ON
ON
Multi-reference 11
FC-11
ON
ON
OFF
OFF
Multi-reference 12
FC-12
ON
ON
OFF
ON
Multi-reference 13
FC-13
ON
ON
ON
OFF
Multi-reference 14
FC-14
ON
ON
ON
ON
Multi-reference 15
FC-15
When the frequency source is selected for MS speed, 100.0% of function code FC-00~ FC-15,
corresponding to the maximum frequency F0-10.
Содержание VD560 Series
Страница 2: ......
Страница 9: ...VD560 Series Inverter User Manual Safety and Precautions 5 damage or performance reduce...