Function Parameter Table VD560 Series Inverter User Manual
- 52 -
motor voltage
F4-15
VF Separation
Voltage Digital
Setting
0V~rated motor voltage
0V
○
F4-16
VF Separation
Voltage Rise
Time
0.0s~1000.0s
Remark: Indication the time that 0V rise
to rated motor voltage
5.0s
○
F4-17
VF Separation
Voltage Fall
Time
0.0s~1000.0s
Remark: Indication the time that rated
motor voltage drop to 0V
5.0s
○
F5 Input Terminal
Function
Code
Parameter
Name
Setting Range
Factory
Default
Value
Property
F5-00
Terminal
Command Mode
0: Two-line mode 1
1: Two-line mode 2
2: Three-line mode 1
3: Three-line mode 2
4: Alternate control
5: Back and forth control
0
◎
F5-01
DI1 Terminal
Function
Selection
1
◎
F5-02
DI2 Terminal
Function
Selection
2
◎
F5-03
DI3 Terminal
Function
Selection
4
◎
F5-04
DI4 Terminal
Function
Selection
6
◎
F5-05
DI5 Terminal
Function
Selection
8
◎
F5-06
HdI1 Terminal
Function
Selection
0
◎
F5-07
DI7 (expansion
card) Terminal
Function
Selection
0
◎
F5-08
DI8 (expansion
card) Terminal
Function
0: No function
1: Forward running (FWD)
2: Reverse running (REV)
3: Three-line mode run control
4: Forward Jog (FJOG)
5: Reverse Jog (RJOG)
6: Coast to stop
7: Run pause
8: Fault reset (RESET)
9: External fault normally open input
10: External fault normally closed input
11: Terminal UP
12: Terminal DOWN
13: UP/DOWN setting clear
14: Switching frequency source
15: Frequency source A switching with
preset frequency
16: Frequency source B switching with
preset frequency
17: MS reference terminal 1
18: MS reference terminal 2
19: MS reference terminal 3
20: MS reference terminal 4
21: Acceleration/deceleration time
0
◎