Parameter Description VD560 Series Inverter User Manual
- 130 -
Hundred’s digit: DI3, same as above
Thousand’s digit: DI4, same as above
Ten thousand’s digit: DI5, same as
above
F5-11
DI1 Terminal Mode
Selection 2 Effectively
Unit’s digit: HDI1
0: High level effective
1: Low level effective
Ten’s digit: reserved
Hundred’s digit: reserved
Thousand’s digit: reserved
0x0000
◎
Used to set the valid state model of digital quantity input terminal.
When selection for high level is valid, the corresponding DI terminal is valid connected with the COM,
and is invalid disconnection.
When selection for low level is valid, the corresponding DI terminal is invalid connected with the COM,
and is valid disconnection.
F5-12
DI Filter Time
0.000s~1.000s
0.010s
○
Set the software filter time of DI terminal state. If the input terminal of the usa occasion is easy to be
interfered an caused by the wrong action, the parameter can be increased to enhance the
anti-interference ability. But the filter time increases can cause DI terminal response slow.
F5-13
DI1 Close Delay Time
0.0s~3600.0s
0.0s
◎
F5-14
DI2 Close Delay Time
0.0s~3600.0s
0.0s
◎
F5-15
DI3 Close Delay Time
0.0s~3600.0s
0.0s
◎
F5-16
DI1 Open Delay Time
0.0s~3600.0s
0.0s
◎
F5-17
DI2 Open Delay Time
0.0s~3600.0s
0.0s
◎
F5-18
DI3 Open Delay Time
0.0s~3600.0s
0.0s
◎
Is used to set DI terminal state changes, delay time of the frequency inverter for the change.
Only DI1, DI2, DI3 have the function that set the delay time at present.
F5-19
Terminal UP/DOWN
change rate
0.001Hz/s~65.535Hz/s
1.000Hz/s
○
Used to set the terminal UP/DOWN to adjust the setting frequency, the speed of frequency change,
that is the frequency variation per second.
When F0-15 (frequency decimal point) is 2, the value range is from 0.001Hz/s to 65.535Hz/s.
When F0-15 (frequency decimal point) is 1, the value range is from 0.01Hz/s to 655.35Hz/s
F5-20
AI Curve Selection
Unit’s digit: AI1 curve selection
1: Curve 1 (2 point, see F5-22~F5-26)
2: Curve 2 (2 point, see F5-27~F5-31)
3: Curve 3 (2 point, see F5-32~F5-36)
4: Curve 4 (4 point, see b2~00-b2-07)
5: Curve 5 (4 point, see b2-08~b2-15)
Ten’s digit: AI2 curve selection, same as
above
0x321
○