VD560 Series Inverter User Manual Function Parameter Table
- 63 -
F8-21
Overspeed
Detection Time
(FVC)
0.0: No detection
0.1s~60.0s
0.0s
○
F8-22
Large Speed
Deviation
Detection Value
(FVC)
0.0%~50.0% (max frequency)
20.0%
○
F8-23
Large Speed
Deviation
Detection Time
(FVC)
0.0: No detection
0.1s~60.0s
0.0s
○
F8-24
Action Selection
Upon
Instantaneous
Power Failure
0: Invalid
1: Decelerate
2: Decelerate to stop
0
○
F8-25
Voltage Restore
Judgment Value
Upon
Instantaneous
Power Failure
F0-10~100.0%
90.0%
○
F8-26
Voltage Restore
Judgment Time
Upon
Instantaneous
Power Failure
0.00s~100.00s
0.50s
○
F8-27
Voltage
Judgment Value
Upon
Instantaneous
Power Failure
60.0%~100.0% (Standard bus voltage)
80.0%
○
F8-28
Encoder
Reverse
Detection Time
0.0: No detection
0.1s~60.0s
0.0s
○
F8-29
Maximum
Change of V/F
Overvoltage Stall
0: No limit
0~30000
800
○
F9 Fault Record and Setting
Function
Code
Parameter
Name
Setting Range
Factory
Default
Value
Property
F9-00
Fault Types for
the First Time
-
●
F9-01
Fault Types for
the Second Time
-
●
F9-02
Fault Types for
the Third Time
(Last Time)
0: No fault
1: Acceleration over current (hardware)
2: Deceleration over current (hardware)
3: Constant speed over current
(hardware)
4: Acceleration over current (software)
5: Deceleration over current (software)
6: Constant speed over current (software)
-
●