VD560 Series Inverter User Manual Function Parameter Table
- 57 -
17: Current 1 reached output
18: Current 2 reached output
19: Zero current state
20: Output current limit exceeded
21: Motor overload pre-alarm
22: Inverter overload pre-alarm
23: During the load
24: Set Count value reached
25: Designated count value reached
26: Length reached
27: Module temperature reached
28: Reserved
29: Current running time reached
30: Accumulative running time reached
31: Accumulative power-on time reached
32: Timing reached output
33: PLC circulation output
34: Frequency limit
35: Torque limit
36: Reverse running
37: AI1 input limit
38: AI1>AI2
39: Communication setting
40: Brake output (power on brake
releasing)
41: Timing braking (power on braking)
42: Inverter in running (jog no output)
F6-06
DO Output
Terminal
Effective State
Selection
Unit’s digit: HDO1
0: Positive logic
1: Anti-logic
Ten’s digit: RELAY1, same as above
Hundred’s digit: RELAY 2, same as above
Thousand’s digit: DO1, same as above
Ten thousand’s digit: DO5 (expansion
card), same as above
0x00000
○
F6-07
HDO1 Closing
Delay
0.0s~3600.0s
0.0s
○
F6-08
T1 Closing
Delay
0.0s~3600.0s
0.0s
○
F6-09
T2 Closing
Delay
0.0s~3600.0s
0.0s
○
F6-10
DO1 Closing
Delay
0.0s~3600.0s
0.0s
○