Vacon Plc
Phone: +358-201 2121
Fax:+358-201 212 205
Service: +358-40-8371 150
E-mail: [email protected]
Page 60
Vacon
Pump and fan control with autochange
Terminal
Signal
Description
206
+24V
Control voltage output
Voltage for switches, etc. max. 0.1 A
207
GND
I/O ground
Ground for reference and controls
208
CMC
Common for DIC1-DIC7
Connect to GND or + 24 V
209
DIC1
Interlock input,
Contact closed = interlock is active
autochange 1
210
DIC2
Interlock input
Contact closed = interlock is active
autochange 2
211
DIC3
Interlock input,
Contact closed = interlock is active
autochange 3
212
DIC4
Interlock input
Contact closed = interlock is active
autochange 4
213
DIC5
Interlock input,
Contact closed = interlock is active
autochange 5
214
GND
I/O ground
Ground for reference and controls
215
I
out
+
Analogue output
Range 0—20 mA /R
L
max. 500
Ω
Programmable
221
TI+
Termistor input
222
TI-
223
RO3
Relay output 3
Aux. drive 1 / Autochange 1 control
224
RO3
225
RO4
Relay output 4
Aux. drive 2 / Autochange 2 control
226
RO4
227
RO5
Relay output 5
Aux. drive 3 / Autochange 3 control
228
RO5
Signal from
motor termistors
Figure 7-2 I/O-Expander 103 OPT with pump and fan control