Page 3
Pump control with autochange
PI-controller
actual value
220
VAC
READY
220
VAC
FAULT
2 Control I/O
Terminal
Signal
Description
1
+10V
ref
Reference output
Voltage for a potentiometer, etc.
2
U
in
+
Analog input, voltage
Programmable
range 0—10 V DC
(factory setting: not in use)
3
GND
I/O ground
Ground for reference and controls
4
I
in
+
Analogue input,
PI-controller actual value
5
I
in
-
current (programmable)
range 4—20 mA
6
+24V
Control voltage output
Voltage for switches, etc. max. 0.1 A
7
GND
Control voltage ground
Ground for reference and controls
8
DIA1
Start/Stop
Contact open = stop
Source A (PI-controller)
Contact closed = start
9
DIA2
Interlock input, autoch. 1
Contact open = no interlock
(programmable)
Contact closed = interlock active
10
DIA3
Interlock input, autoch. 2
Contact open = no interlock
(programmable)
Contact closed = interlock active
11
CMA
Common for DIA1—DIA3
Connect to GND or + 24V
12
+24V
Control voltage output
Voltage for switches, (same as #6)
13
GND
I/O ground
Ground for reference and controls
14
DIB4
Start/Stop
Contact open = stop
Source B (Direct freq. ref.) Contact closed = start
15
DIB5
Jogging speed select
Contact open = no action
(programmable)
Contact closed = jogging speed
16
DIB6
Source A/B selection
Contact open = source A is active
Contact closed = source B is active
17
CMB
Common for DIB4—DIB6
Connect to GND or + 24V
18
I
out
+
Analogue output
Programmable (par. 3
.
1)
19
I
out
-
Output frequency
Range 0—20 mA/R
L
max. 500
Ω
20
DO1
Digital output
Programmable ( par. 3
.
6)
FAULT
Open collector, I<50 mA, U<48 VDC
21
RO1
Relay output 1
Contact closed = control active
22
RO1
Autochange 1
Programmable ( par. 3
.
7)
23
RO1
control
24
RO2
Relay output 2
Contact closed = control active
25
RO2
Autochange 2
Programmable ( par. 3
.
8 )
26
RO2
control
Figure 2-1
Default I/O configuration and connection example of the Pump and fan
Control Application with autochange
converter controls the speed of the variable
speed drive and gives control signals to Start
and Stop auxiliary drives to control the total
flow.
The application has two control sources on
I/O terminals. Source A is Pump and fan
control and source B is direct frequency
reference. The control source is selected with
DIB6 input.
1 General
Pump and fan control with autochange can be
selected by setting the value of parameter 0.1
to 0.
The application can be used to control one
variable speed drive and 0-4 auxiliary drives.
Additionally the motor connected to the
frequency converter and the start order of the
auxiliary drives can be changed with the
autochange function and external relay
system. The PI-controller of the frequency
Note! Remember to connect CMA and CMB inputs