Pump and fan control with autochange
Code
Parameter
Range
Step
Default
Custom
Description
Page
2
.
26
Direct frequency
0—4
1
0
0 = U
in
signal (control board)
24
reference, source B
1 = I
in
signal (control board)
2 = Set reference from the panel
(reference r1)
3 = Signal from internal motor pot.
4 = Signal from internal motor pot.
reset if Vacon unit is stopped
2
.
27
Source B reference
0—par.2
.
28
1 Hz
0 Hz
Selects the frequency that corres-
24
scaling minimum value
ponds to the min. refer. signal
2
.
28
Source B reference
par.2
.
28
1 Hz
0 Hz
Selects the frequency that
24
scaling maximum value
—f
max
corresponds to the max.
reference signal
0 = Scaling off
>0 = Scaled maximum value
2
.
29
PI-controller
0—7
1
7
0 = U
in
signal (control board)
25
reference 2
1 = I
in
signal (control board)
2 = Set reference from the panel
(reference r2)
3 = Signal from internal motor pot.
4 = Signal from internal motor pot.
reset if Vacon unit is stopped
5 = Option board Ain1-signal
6 = Option board Ain2-signal
7 = Set reference from the panel
(reference r3)
2
.
30
Option board Ain1 signal
0—1
1
0
0 = Not inverted
25
inversion
1 = Inverted
2
.
31
Option board Ain1 signal
0—10s
0.01s
0.1s
0 = No filtering
25
filter time
2
.
32
Option board Ain2 signal
0—2
1
0
0 = 0—20 mA
25
signal range
1 = 4—20 mA
2 = 0—10 V
2
.
33
Option board Ain2 signal
0—1
1
0
0 = Not inverted
25
inversion
1 = Inverted
2
.
34
Option board Ain2 signal
0 —10s
0.01s
0.1s
0 = No filtering
25
filter time
Note!
= Parameter value can be changed only when the frequency converter is stopped (Continues)