Pump control with autochange
6.2 Description of Groups 2—9 parameters
2. 1
DIA2 function
1:
External fault, closing contact = Fault is shown and motor is stopped when
the input is active
2:
External fault, opening contact = Fault is shown and motor is stopped when
the input is not active
3:
Run enable
contact open
= Start of the motor disabled
contact closed
= Start of the motor enabled
4:
Acc. / Dec
contact open
= Acceleration/Deceleration time 1 selected
time select.
contact closed
= Acceleration/Deceleration time 2 selected
5:
Reverse
contact open
= Forward
If two or more inputs are progr.
contact closed
= Reverse
to reverse then if one of them is
active the direction is reverse
6:
Jogging freq.
contact closed
= Jogging frequency selected for freq. refer.
7:
Fault reset
contact closed
= Resets all faults
8:
Acc./Dec.
contact closed
= Stops acceleration and deceleration until
operation
the contact is opened
prohibited
9:
DC-braking
contact closed
= In the stop mode, the DC-braking operates
command
until the contact is opened, see figure 6-1.
Dc-brake current is set with parameter 4
.
8.
10:
Motor pot.
contact closed = Reference increases until the contact is
UP
opened
11:
Interlock inp., contact closed = Interlock of autochange drive 1 is active
autochange 1
Figure 6-1 DIA3 as DC-brake
command input:
a) Stop-mode = ramp,
b) Stop-mode = coasting
t
UD009K32
Param. 4
.
10
DIA3
t
UD009K32
DIA3
RUN
STOP
Output
frequency
DIA3 as DC-brake command input and stop-mode = Ramp
DIA3 as DC-brake command input and stop-mode = Coasting