background image

Vacon Plc

Phone: +358-201 2121

Fax:+358-201 212 205

Service: +358-40-8371 150

E-mail: [email protected]

E-mail: [email protected]

Vacon

           Page 21

Pump control with autochange

6.2   Description of Groups 2—9 parameters

2. 1

DIA2 function

1:

External fault, closing contact = Fault is shown and motor is stopped when

   the input is active

2:

External fault, opening contact = Fault is shown and motor is stopped  when

   the input is not active

3:

Run enable

contact open

= Start of the motor disabled

contact closed

= Start of the motor enabled

4:

Acc. / Dec

contact open

= Acceleration/Deceleration time 1 selected

time select.

contact closed

= Acceleration/Deceleration time 2 selected

5:

Reverse

contact open

= Forward

If two or more inputs are progr.

contact closed

= Reverse

to reverse then if one of  them is
active the direction is reverse

6:

Jogging freq.

contact closed

= Jogging frequency selected for freq. refer.

7:

Fault reset

contact closed

= Resets all faults

8:

Acc./Dec.

contact closed

= Stops acceleration and deceleration until

operation

   the contact is opened

prohibited

9:

DC-braking

contact closed

= In the stop mode, the DC-braking operates

command

   until the contact is opened, see figure 6-1.
   Dc-brake current is set with parameter 4

.

 8.

10:

 Motor pot.

 contact closed = Reference increases until  the contact is

 UP

    opened

11:

  Interlock inp.,  contact closed  = Interlock of autochange drive 1 is active

      autochange 1

Figure  6-1 DIA3 as DC-brake
command input:
a) Stop-mode = ramp,
b) Stop-mode = coasting

t

UD009K32

Param. 4

.

 10

DIA3

t

UD009K32

DIA3

RUN
STOP

Output 
frequency

DIA3 as DC-brake command input and stop-mode = Ramp

DIA3 as DC-brake command input and stop-mode = Coasting

Содержание CX

Страница 1: ...F O R S M O O T H C O N T R O L P u m p c o n t r o l w i t h a u t o c h a n g e Subject to changes without notice V A C O N C X C X L C X S F R E Q U E N C Y C O N V E R T E R S ...

Страница 2: ...eneral 3 2 Control I O 3 3 Control signal logic 4 4 Parameter group 0 5 5 Basic parameters Group 1 6 5 1 Parameter table Group 1 6 5 2 Description of Group1 parameters 7 6 Special parameters Groups 2 10 10 6 1 Parameter tables Groups 2 10 10 6 2 Description of Groups 2 10 param 21 7 I O expander with pump and fan control 59 8 Commissioning of pump and fan control 62 9 Monitoringdata 63 10 Panel re...

Страница 3: ...ogrammable Contact closed jogging speed 16 DIB6 Source A B selection Contact open source A is active Contact closed source B is active 17 CMB Common for DIB4 DIB6 Connect to GND or 24V 18 Iout Analogue output Programmable par 3 1 19 Iout Output frequency Range 0 20 mA RL max 500 Ω 20 DO1 Digital output Programmable par 3 6 FAULT Open collector I 50 mA U 48 VDC 21 RO1 Relay output 1 Contact closed ...

Страница 4: ...DIA2 DIB6 DIA3 DIA1 P P DIB4 P I D IA3 DIA2 pfcauto fh3 R ST PG RO1 RO2 Internal frequency reference Internal Start Stop controlline signalline D ow n PR OG RAMMABLE PU SH BUT TON 2 Motorised potentio meter reference Autochange 2 PARAMET ERS 2 26 Source B ref select 2 15 Source A ref select 4 12 Jogging speed ref PI controller Refe ren ce S ource A Freq ref Source B Actual value Up Actual value se...

Страница 5: ...p to the panel possible only with graphical panel 5 Load down parameters from panel possible only with graphical panel 0 3 Language selection 0 1 1 0 0 English 1 Finnish 2 Spanish 4 Parameter group 0 0 1 Application selection With this parameter the active application can be selected If the device has been ordered from the factory equipped with pump and fan control with autochange application this...

Страница 6: ... V Vacon range CX CXL2 8 of the motor 400 V Vacon range CX CXL CXS4 500 V Vacon range CX CXL CXS5 690 V Vacon range CX6 1 11 Nominal frequency 30 500 Hz 1 Hz 50 Hz fn from the rating plate of 8 of the motor the motor 1 12 Nominal speed 1 20000 rpm 1 rpm 1440 rpm nn from the rating plate of 8 of the motor the motor 1 13 Nominal current 2 5 x In CX 0 1 A InCX In from the rating plate of 8 of the mot...

Страница 7: ...f the PI controller If this parameter is set to 100 a 10 change in error value causes the controller output to change by 10 0 Hz If the parameter value is set to 0 the PI controller operates as I controller 1 6 PI controller I time Defines the integration time of the PI controller 1 7 Current limit This parameter determines the maximum motor current from the frequency converter To avoid motor over...

Страница 8: ...timization Automatic The voltage to the motor changes automatically which makes the torque motor to produce torque enough to start and run at low frequencies boost The voltage increase depends on the motor type and power Automatic torque boost can be used in applications where starting torque is high due to starting friction e g in conveyors NOTE In high torque low speed applications it is likely ...

Страница 9: ...eakening point parameter 6 3 to the same value 1 12 Nominal speed of the motor Find this value nn on the rating plate of the motor 1 13 Nominal current of the motor Find this value In on the rating plate of the motor 1 14 Supply voltage Set parameter value according to the nominal voltage of the supply Values are pre defined for CX CXL2 CX CXL CXS4 CX CXL CXS5 and CX6 ranges see table 6 4 1 1 15 P...

Страница 10: ...mmand 10 Motor potentiometer DOWN 11 Interlock input autochange 2 2 3 Uin signal range 0 2 1 0 0 0 10 V 21 1 Custom setting range 2 2 10 V 2 4 Uin custom setting min 0 100 0 01 0 00 21 2 5 Uin custom setting max 0 100 0 01 100 00 21 2 6 Uin signal inversion 0 1 1 0 0 Not inverted 21 1 Inverted 2 7 Uin signal filter time 0 10s 0 01s 0 1s 0 No filtering 21 2 8 Iin signal range 0 2 1 1 0 0 20 mA 21 1...

Страница 11: ...ual2 7 SQRT Act1 SQRT Act2 2 17 Actual value 1 input 0 4 1 2 0 No 23 1 Uin signal control board 2 Iin signal control board 3 Option board Ain1 signal 4 Option board Ain2 signal 5 Fieldbus signal 2 18 Actual value 2 input 0 4 1 0 0 No 23 1 Uin signal control board 2 Iin signal control board 3 Option board Ain1 signal 4 Option board Ain2 signal 2 19 Actual value 1 320 00 0 01 0 0 no minimum scaling ...

Страница 12: ...responds to the max reference signal 0 Scaling off 0 Scaled maximum value 2 29 PI controller 0 7 1 7 0 Uin signal control board 25 reference 2 1 Iin signal control board 2 Set reference from the panel reference r2 3 Signal from internal motor pot 4 Signal from internal motor pot reset if Vacon unit is stopped 5 Option board Ain1 signal 6 Option board Ain2 signal 7 Set reference from the panel refe...

Страница 13: ...6 3 6 Digital output function 0 30 1 3 0 Not used 27 1 Ready 2 Run 3 Fault 4 Fault inverted 5 Vacon overheat warning 6 External fault or warning 7 Reference fault or warning 8 Warning 9 Reversed 10 Jogging speed selected 11 At speed 12 Motor regulator activated 13 Output freq limit superv 1 14 Output freq limit superv 2 15 Torque limit supervision 16 Reference limit supervision 17 External brake c...

Страница 14: ... 29 3 18 External brake on delay 0 100 0 s 1 0 5 s 29 3 19 Frequency converter 0 2 1 0 0 No 30 temperature limit 1 Low limit supervision function 2 High limit 3 20 Frequency converter 10 75 C 1 40 C 30 temperature limit 3 21 I O expander board opt 0 7 1 3 See parameter 3 1 30 analogue output content 3 22 I O expander board opt 0 01 10 s 0 01 1 00 See parameter 3 2 30 analogue output filter time 3 ...

Страница 15: ...X 4 9 DC braking time at Stop 0 250 00 s 0 01 s 0 s 0 DC brake is off at Stop 33 4 10 Execute frequency of DC 0 1 Hz 1 5 Hz 34 brake during ramp stop 4 11 DC brake time at Start 0 250 00 s 0 01 s 0 s 0 DC brake is off at Start 34 4 12 Jogging speed reference fmin fmax 0 1 Hz 10 0 Hz 34 1 1 1 2 Group 5 Prohibit frequency parameters Code Parameter Range Step Default Custom Description Page 5 1 Prohi...

Страница 16: ...tage controller 0 1 1 1 0 Controller is not operating 36 1 Controller is in operation Group 7 Protections Code Parameter Range Step Default Custom Description Page 7 1 Response to 0 3 1 2 0 No action 36 reference fault 1 Warning 2 Fault stop according to par 4 7 3 Fault stop always by coasting 7 2 Response to 0 3 1 0 0 No action 36 external fault 1 Warning 2 Fault stop according to par 4 7 3 Fault...

Страница 17: ...load time 2 0 600 0 s 1 0 s 20 0s 41 7 18 Phase supervision of 0 2 2 2 0 No action 42 the supply voltage 2 Fault 7 19 Termistor input of 0 2 1 2 0 No action 42 I O Expander 1 Warning 2 Fault 7 20 Fieldbus fault 0 2 1 2 0 No action 1 Warning 2 Fault Group 8 Autorestart parameters Code Parameter Range Step Default Custom Description Page 8 1 Automatic restart 0 10 1 2 0 Not used 42 number of tries 8...

Страница 18: ...Hz 10 0 Hz Needs I O expander option board 44 auxiliary drive 4 Par 9 8 9 10 Start delay of the 0 300 0 s 0 1 s 4 0 s 44 auxiliary drives 9 11 Stop delay of the 0 300 0 s 0 1 s 2 0 s 44 auxiliary drives 9 12 Reference step after 0 100 0 0 1 0 0 In of actual value 45 start of the 1 aux drive 9 13 Reference step after 0 100 0 0 1 0 0 In of actual value 45 start of the 2 aux drive 9 14 Reference step...

Страница 19: ... 0 0 s 0 0 no delay 50 delay after stopping 0 1 299 0 delay value an auxiliary drive 300 0 no frequency increase 9 27 Autochange mode 0 2 1 2 0 autochange off 51 1 autochange only with auxiliary drives 2 autochange with all drives 9 28 Autochange interval 0 1 3000 h 0 1 h 50 0 h Elapsed time for autochange 52 0 Test interval 40 secs 9 29 Autochange level 0 4 1 0 Determines how many auxiliary 53 au...

Страница 20: ...aud 5 4800 baud 6 9600 baud 7 19200 baud 10 4 Modbus parity type 0 2 1 1 0 None 56 1 Even 2 Odd 10 5 Modbus time out 0 3600 1s 0s 0 No time out 56 s 10 6 Profibus slave address 2 126 1 2 57 10 7 Profibus baud rate 1 10 1 10 1 9 6 kbaud 57 2 19 2 kbaud 3 93 75 kbaud 4 187 5 kbaud 5 500 kbaud 6 1 5 Mbaud 7 3 Mbaud 8 6 Mbaud 9 10 AUTO 10 8 Profibus PPO type 1 4 1 1 1 PPO1 57 2 PPO2 3 PPO3 4 PPO4 10 9...

Страница 21: ...are progr contact closed Reverse to reverse then if one of them is active the direction is reverse 6 Jogging freq contact closed Jogging frequency selected for freq refer 7 Fault reset contact closed Resets all faults 8 Acc Dec contact closed Stops acceleration and deceleration until operation the contact is opened prohibited 9 DC braking contact closed In the stop mode the DC braking operates com...

Страница 22: ...rameter 2 4 press the Enter button Maximum setting Set the Uin signal to its maximum level select parameter 2 5 press the Enter button Note The parameter values can only be set with this procedure not with arrow up arrow down buttons 2 6 Uin signal inversion Parameter 2 6 1 inversion of analogue Uin signal 2 9 Analogue input Iin custom setting 2 10 minimum maximum With these parameters you can sca...

Страница 23: ...t closed Start of the motor enabled 4 Acc Dec contact open Acceleration Deceleration time 1 selected time select contact closed Acceleration Deceleration time 2 selected 5 Reverse contact open Forward If two or more inputs are contact closed Reverse programmed to reverse then if one of them is active the direction is reverse 6 Jogging freq contact closed Jogging frequency selected for freq refer 7...

Страница 24: ...rent signal Vacon CX 100 OPT voltage signal Vacon CX 102 OPT 7 Fieldbus signal 2 16 PI controller actual value selection 0 Actual value 1 1 Sum of Actual value 1 and Actual value 2 2 Difference of Actual value 1 and Actual value 2 3 Multiplication of Actual value 1 and Actual value 2 4 Minor of signals Actual value 1 and Actual value 2 is active actual value 5 Major of signals Actual value 1 and A...

Страница 25: ...e reference from terminals 2 3 e g a potentiometer 1 Analogue current reference from terminals 4 5 e g a transducer 2 Panel reference is the reference set from the Reference Page REF Reference r1 is the Place B reference see chapter 6 3 Reference value is changed with digital input signals DIA2 and DIA3 switch in DIA2 closed frequency reference increases switch in DIA3 closed frequency reference d...

Страница 26: ... the parameter 2 1 is automatically set to 4 and value of the parameter 2 2 is automatically set to 10 5 Analogue voltage signal from the terminals 202 203 of the I O expander 6 Analogue signal from the terminals 204 205 of the I O expander current signal Vacon CX 100 OPT voltage signal Vacon CX 102 OPT 7 Panel reference r3 can be set on the Reference Page REF of the panel 2 30 Ain1 signal inversi...

Страница 27: ... mA or 4 mA living zero See figure 6 9 3 5 Analogue output scale Scaling factor for analogue output See figure 6 9 Signal Max value of the signal Output freq Max frequency p 1 2 Motor speed Max speed nn xfmax fn Output 2 x InCX current Motor torque 2 x TnCX Motor power 2 x PnCX Motor voltage 100 x Unmotor DC link volt 1000 V PI ref value 100 x ref value max PI act value1 100 x act value max PI act...

Страница 28: ...mit par 3 13 and par 3 14 16 Active reference Active reference goes beyond the set supervision limit supervision Low limit High limit par 3 15 and par 3 16 17 External brake control External brake ON OFF control with programmable de lay par 3 17 and 3 18 18 Control from I O terminals External control mode selected with pr push button 2 19 Frequency converter Temperature on frequency converter goes...

Страница 29: ... 2 control Control signal for drive 2 in autochange system 27 Autochange 5 control Control signal for drive 5 in autochange system with I O expander option 28 Auxiliary drive 1 start Starts and stops auxiliary drive 1 29 Auxiliary drive 2 start Starts and stops auxiliary drive 2 30 Auxiliary drive 3 start Starts and stops auxiliary drive 3 Table 6 3c Output signals via RO2 3 9 Output frequency lim...

Страница 30: ...trol source 3 16 Active reference limit supervision value The frequency value to be supervised by the parameter 3 15 3 17 External brake off delay 3 18 External brake on delay With these parameters the timing of external brake can be linked to the Start and Stop control signals see figure 6 11 The brake control signal can be programmed via the digital output DO1 or via one of relay outputs RO1 and...

Страница 31: ...ogue outputs See figure 6 12 3 28 Analogue input supervision input signal selection 0 Analogue voltage signal from terminals 2 3 1 Analogue current signal from terminals 4 5 2 Analogue voltage signal from terminals 202 203 of the I O expander 3 Analogue signal from the terminals 204 205 of the I O expander current signal Vacon CX 100 OPT voltage signal Vacon CX 102 OPT 3 29 Analoque input supervis...

Страница 32: ...rrespond to the time required for the output frequency to accelerate from the set minimum frequency par 1 1 to the set maximum frequency par 1 2 These times give the possibility to set two different acceleration deceleration time sets for one application The active set can be selected with the programmable signal DIA3 of this application see parameter 2 2 Acceleration deceleration times can be red...

Страница 33: ...ency towards the actual frequency until the correct value is detected Thereafter the output frequency will be accelerated decelerated to the set reference value according to the set acceleration deceleration parameters Use this mode if the motor may be coasting when the start command is given With the flying start it is possible to ride through short mains voltage interruptions 4 7 Stop function C...

Страница 34: ...ccording to the frequency when the DC braking starts If the frequency is nominal frequency of the motor par 1 11 the setting value of parameter 4 9 determines the braking time When the frequency is 10 of the nominal the braking time is 10 of the set value of parameter 4 9 Stop function 1 ramp After the Stop command the speed of the motor is reduced according to the set deceleration para meters as ...

Страница 35: ...gure 6 16 Figure 6 16 DC braking time at start 4 10 Execute frequency of DC brake during ramp Stop t UD009K22 Par 4 11 RUN STOP Output frequency 5 1 Prohibit frequency area 5 2 Low limit High limit 5 3 5 4 5 5 5 6 In some systems it may be necessary to avoid certain frequencies because of mechanical resonance problems With these parameters it is possible to set limits for three skip frequency regi...

Страница 36: ...figure 6 18 When the parameters 1 10 and 1 11 nominal voltage and nominal frequency of the motor are set also parameters 6 3 and 6 4 are set automatically to the corresponding values If different values for the field weakening point and the maximum output voltage are required change these parameters after setting the parameters 1 10 and 1 11 6 5 U f curve middle point frequency If the programmable...

Страница 37: ...g 2 Fault stop mode after fault according to parameter 4 7 3 Fault stop mode after fault always by coasting A warning or a fault action and message is generated from the external fault signal in the digital input DIA3 The information can also be programmed into digital output DO1 and into relay outputs RO1 and RO2 7 3 Phase supervision of the motor 0 No action 2 Fault Phase supervision of the moto...

Страница 38: ...l stage is determined with the time constant parameter 7 8 The bigger the motor the longer it takes to reach the final temperature The thermal stage of the motor can be monitored through the display Refer to the table for monitoring items User s Manual table 7 3 1 CAUTION The calculated model does not protect the motor if the airflow to the motor is reduced by blocked air intake grill 7 5 Motor th...

Страница 39: ...put current of the drive Parameter 1 7 alone determines the maximum output current of the drive 7 8 Motor thermal protection time constant The time can be set between 0 5 300 minutes T h i s is the thermal time constant of the motor The bigger the motor the bigger the time constant The time constant is the time when the calculated thermal stage has reached 63 of its final value parameter could be ...

Страница 40: ...or temperature Time Motor temperature Time constant T Changed with motor size and adjusted with parameter 7 8 Trip warning Motor current 7 10 Stall protection Operation 0 Not in use 1 Warning 2 Trip function Tripping and warning will display the same message code If the tripping is set on the drive will stop and activate the fault stage Setting the parameter to 0 will deactivate the protection and...

Страница 41: ...weakening point The protection is not active below 5Hz the underload counter value is stopped Refer to the figure 6 23 The torque values for setting the underload curve are set in percentage which refer to the nominal 7 11 Stall current limit The current can be set between 0 0 200 x InMotor In the stall stage the current has to be above this limit Refer to the figure6 21 The value is set as a perc...

Страница 42: ... This parameter gives the value for the minimum allowed torque when the output frequency is above the field weakening point Refer to the figure 6 23 If parameter 1 13 is adjusted this parameter is automatically restored to the default value Figure 6 23 Setting of minimum load 7 16 Underload protection zero frequency load The torque limit can be set between 10 0 150 x TnMotor This parameter gives v...

Страница 43: ...erature can be programmed 7 20 Fieldbus fault 0 No action 1 Warning 2 Fault 8 1 Automatic restart number of tries 8 2 Automatic restart trial time The Automatic restart function restarts the frequency converter after the faults selected with parameters 8 4 8 8 The Start function for Automatic restart is selected with parameter 8 3 Parameter 8 1 determines how many automatic restarts can be made du...

Страница 44: ...DC link voltage returns to the normal level 8 5 Automatic restart after overvoltage trip 0 No automatic restart after overvoltage trip 1 Automatic restart after overvoltage fault condition returns to the normal condition DC link voltage returns to the normal level 8 6 Automatic restart after overcurrent trip 0 No automatic restart after overcurrent trip 1 Automatic restart after overcurrent faults...

Страница 45: ...auxiliary drive is started The 1 Hz overdraft makes a hysteresis to avoid unnecessary starts and stops See figure 6 26 Notice See the parameter description par 1 1 and 1 2 page 6 9 3 Stop frequency of auxiliary drive 1 9 5 Stop frequency of auxiliary drive 2 9 7 Stop frequency of auxiliary drive 3 The frequency of the drive controlled by the frequency converter must fall with 1Hz below the limit d...

Страница 46: ... start of the auxiliary drive 4 The reference step will be automatically added to the reference value always when the corresponding auxiliary drive is started With the reference steps e g the pressure loss in the piping caused by the increased flow can be compensated See figure 6 27 Time Reference for PI controller Reference analoginput Reference step 1 par 9 12 Reference step 2 par 9 13 Reference...

Страница 47: ...state when the wake up level defined with parameters 9 18 and 9 19 is reached See figure 6 28 9 18 Wake up level The wake up level defines the level below which the actual value must fall or which has to be exceeded before starting the frequency converter from the sleep function See figure 6 28 t tsleep param 9 17 tsleep Wake up level param 9 18 Actual value Output frequency Sleep level param 9 16...

Страница 48: ... 60 limit 60 refrence 30 refrence 50 time Start Stop Actual value signal Actual value signal The limit defined with parameter 9 18 is procents from the current value of the reference signal The limit defined with parameter 9 18 is procents from the current value of the reference signal Start Stop time Actual value signal The limit defined with parameter 9 18 is procents from the maximum value of t...

Страница 49: ...liary drives are defined according to the actual value signal Minimum freq par 1 1 Minimum of the actual value Output freq Actual value Maximum of the actual value Start freq of the aux drive 1 par 9 2 Max freq par 1 2 Stop freq of the aux drive 1 par 9 3 Stop freq of the aux drive 2 par 9 5 Start stop control of the freq converter Auxiliary drive 1 stop start stop start stop start Start freq of t...

Страница 50: ...with parameter 9 21 See figure 6 30 With parameters 9 22 and 9 23 the limits for the area of the input pressure where the output pressure is decreased can be selected Values are in percentage of the input pressure measurement maximum value With parameter 9 24 the value for output pressure decrease in this area can be set The value is percents of the reference value maximum See Figure 6 31 M Vacon ...

Страница 51: ...ake the control smoother Also if the speed of the auxiliary drives decreases slowly soft starter control then with parameter 9 26 a delay between auxiliary drive stop and the frequency increase of the variable speed drive can be programmed See figure 6 32 If either value of parameters 9 25 and 9 26 is maximum 300 0 s then there is no frequency drop nor increase Figure 6 32 Frequency drop and incre...

Страница 52: ...cting the autochange mode with parameter 9 27 The autochange happens when the time period set by parameter 9 28 is elapsed and the level of used capacity is below the limit defined with parameters 9 29 and 9 30 During the autochange moment all drives are stopped and then started with new order External contactors controlled by the relay outputs of the frequency converter connect the drives to the ...

Страница 53: ...onverter is needed See figure 6 34 Vacon M M Drive 1 Drive 2 auxiliary contact connection auxiliary contact connection Figure 6 34 Autochange with all drives 9 28 Autochange interval The parameter defines the time period after which the autochange will be done if the used capacity is below the limit defined with parameters 9 29 and 9 30 If the level is over the limit wait the level to decrease bel...

Страница 54: ...arameter 9 29 the autochange can happen If the number of running auxiliary drives is equal to par 9 29 and the frequency of the variable speed drive is less than the value of parameter 9 30 the autochange can happen If the parameter 9 30 0 0 Hz then the autochange can happen only in sleep or stop state in spite of the value of parameter 9 29 Kuva 6 35 Autochange interval and level vuorot3 fh3 Time...

Страница 55: ...nterlock inputs Each drive must have own interlock input Pump and fan control controls only those motors whose interlock input is active If the interlock input changes to inactive or comes active again in Run state then pump and fan control stops all motors and then starts control with new composi tion If the intelock of auxiliary drives comes true via RUN mode operation depends on par 9 35 settin...

Страница 56: ...Principal control diagram of two pump autochange 9 32 Actual value special display minimum 9 33 Actual value special display maximum 9 34 Actual value special display number of decimals With these parameters the minimum and maximum values and also the number of decimals of the actual value special display can be set The actual value can be found on the monitoring page with signal number n26 3 0 0 ...

Страница 57: ...r and other auxiliary drives are in RUN state 10 Fieldbus control Fieldbus control can be activated with parameter 10 1 Then the frequency or speed refer ence comes from the fieldbus as well as the Start Stop and Reverse control First two parameters in group 10 concern all fieldbuses Parameters 10 3 10 6 are only for Modbus parameters 10 7 10 13 only for Profibus and 10 14 only for LONWorks 10 1 F...

Страница 58: ...us PPO Type Selection of profibus PPO type 1 PPO 1 Parameter data 8 bytes Control data 4 bytes 2 PPO 2 Parameter data 8 bytes Control data 4 bytes 3 PPO 3 Control data 4 bytes 4 PPO 4 Control data 12 bytes 10 9 Profibus process Data 1 10 10 Profibus process Data 2 10 11 Profibus process Data 3 10 12 Profibus process Data 4 Selection of profibus process data source Value 1 22 Number of actual value...

Страница 59: ...ue input current Programmable 205 Iin range 0 20 mA Default Not in use 206 24V Control voltage output Voltage for switches etc max 0 1 A 207 GND I O ground Ground for reference and controls 208 CMC Common for DIC1 DIC7 Connect to GND or 24 V 209 DIC1 Interlock input Contact closed interlock is active autochange 1 210 DIC2 Interlock input Contact closed interlock is active autochange 2 211 DIC3 Int...

Страница 60: ... is active autochange 2 211 DIC3 Interlock input Contact closed interlock is active autochange 3 212 DIC4 Interlock input Contact closed interlock is active autochange 4 213 DIC5 Interlock input Contact closed interlock is active autochange 5 214 GND I O ground Ground for reference and controls 215 Iout Analogue output Range 0 20 mA RL max 500 Ω Programmable 221 TI Termistor input 222 TI 223 RO3 R...

Страница 61: ...ontact closed interlock is active autochange 4 213 Not used 214 DIE6A Interlock input Contact closed interlock is active 215 DIE6A autochange 5 216 DIE7B 217 DIE7B 218 DOE1 219 DOE2 220 Not used 221 TI Termistor input 222 TI 225 RO4 1 Aux drive 3 autochange 3 control 226 RO4 2 231 DOE3 Open collector output 3 Aux drive 1 autochange 1 control 232 GND I O ground 233 DOE4 Open collector output 4 Aux ...

Страница 62: ...I O ground Ground for reference and controls 309 DID5A Interlock input Contact closed interlock is active 310 DID5A autochange 5 311 DID6B 312 DID6B 313 DID7Z 314 DID7Z 315 GND I O ground Ground for reference and controls 316 DOD1 Open collector output 1 Aux drive 1 autochange 1 control 317 DOD2 Open collector output 2 Aux drive 2 autochange 2 control 318 DOD3 Open collector output 3 Aux drive 3 a...

Страница 63: ...I O ground Ground for reference and controls 309 DID5A Interlock input Contact closed interlock is active 310 DID5A autochange 5 311 DID6B 312 DID6B 313 DID7Z 314 DID7Z 315 GND I O ground Ground for reference and controls 316 DOD1 Open collector output 1 Aux drive 1 autochange 1 control 317 DOD2 Open collector output 2 Aux drive 2 autochange 2 control 318 DOD3 Open collector output 3 Aux drive 3 a...

Страница 64: ...hes etc max 0 1 A 307 COME Common for DIE3 DIE4 Connect to GND or 24 V 308 GND I O ground Ground for reference and controls 309 DID5A Pulse input A 310 DID5A differential input 311 DID6B Pulse input B 90 degrees phase shift compared 312 DID6B differential input to pulse input A 313 DID7Z Pulse input Z one pulse per one revolution 314 DID7Z differential input 315 GND I O ground Ground for reference...

Страница 65: ...gure 7 6 Example of 3 pump autochange system main diagram PE L1 L2 L3 U V W PE U V W PE M1 M2 F1 F2 F3 VACON U V W L1 L2 L3 Q1 K1 K2 K1 1 K2 1 M M 3 3 U V W PE M2 F2 K3 K3 1 M 3 ac3maint ds4 223 224 206 209 A O V A O V 225 226 230 VAC S1 K1 K1 1 K1 1 K2 K2 K1 VACON I O expander K1 K2 K2 K2 1 M1 Vacon M2 Vacon M2 mains M1 mains 24 VDC S2 K3 K3 K2 1 K1 K3 210 K3 227 228 A O V S3 K3 K3 1 K3 1 K2 K2 K...

Страница 66: ...g values of parameters 3 6 3 8 to 3 6 Autochange 3 control 27 Digital output 3 7 Autochange 1 control 26 Relay output 1 3 8 Autochange 2 control 26 Relay output 2 If the Autochange is only with auxiliary drives par 9 27 1 then the outputs are auxiliary drive control signals In the beginning the Autochange 1 control is the control signal of the first auxiliary drive If all drives are included to th...

Страница 67: ... hours not resettable V12 MW hours MWh MW hours can be reset with programmable trip counter button 4 V13 Voltage analogue input V Voltage of the terminal Uin term 2 V14 Current analogue input mA Current of terminals Iin and Iin term 4 5 V15 Digital input status gr A V16 Digital input status gr B V17 Digital and relay output status V18 Control program Version number of the control software V19 Unit...

Страница 68: ...ler on the panel s reference page See table 10 1 Reference reference range step Function number name r1 Frequency fmin fmax 0 01 Hz Reference for panel control and reference I O terminal Source B reference r2 PI controller 0 100 0 1 Reference for PI controller reference r3 PI controller 0 100 0 1 Reference for PI controller reference Can be programmed to PI controller reference 2 that can be selec...

Страница 69: ...Vacon Plc Phone 358 201 2121 Fax 358 201 212 205 Service 358 40 8371 150 E mail vacon vacon com E mail application team vacon com Vacon Page 69 Pump control with autochange Remarks ...

Страница 70: ...V ACONPLC P O Box 25 Runsorintie 7 FIN 65381 VAASA FINLAND Phone 358 201 2121 Fax 358 201 212 205 Service 358 40 8371 150 E mail vacon vacon com http www vacon com Distributor U D 00178G 12 4 2001 ...

Отзывы: