Pump control with autochange
Terminal
Signal
Description
206
+24V
Control voltage output
Voltage for switches, etc. max. 0.1 A
207
GND
I/O ground
Ground for reference and controls
208
COME
Common for DIC1-DIC7
Connect to GND or + 24 V
209
DIE1
Interlock input,
Contact closed = interlock is active
autochange 1
210
DIE2
Interlock input
Contact closed = interlock is active
autochange 2
211
DIE3
Interlock input,
Contact closed = interlock is active
autochange 3
212
DIE4
Interlock input
Contact closed = interlock is active
autochange 4
213
Not used
214
DIE6A+
Interlock input
Contact closed = interlock is active
215
DIE6A-
autochange 5
216
DIE7B+
217
DIE7B-
218
DOE1
219
DOE2
220
Not used
221
TI+
Termistor input
222
TI-
225
RO4/1
Aux. drive 3 / autochange 3 control
226
RO4/2
231
DOE3
Open collector output 3
Aux. drive 1 / autochange 1 control
232
GND
I/O ground
233
DOE4
Open collector output 4
Aux. drive 2 / autochange 2 control
234
GND
I/O ground
Figure 7-2 I/O-Expander 202OPT with pump and fan control (Profibus)
Signal from
motor termistor
NOTE!
Termistor input (terminals 327 and 328) must be shorted if not used.
READY = ON, when mains voltage has been applied and Vacon CX is ready to operate.
RUN = ON, when motor is running.
FAULT = ON, if a fault occurs.
FIELDBUS CONTROL = ON, when the fieldbus board is the Active Control Source.