Pump control with autochange
2. 11
Analogue input I
in
inversion
Parameter 2
.
11 = 1, inversion of I
in
input.
2. 12
Analogue input I
in
filter time
Filters out disturbances from the
incoming analogue I
in
signal.
Long filtering time makes
regulation response slower.
See figure 6-3.
Figure 6-3 Analogue input I
in
filter
time
%
100%
63%
Par. 2
.
12
t [s]
UD009K30
Filtered signal
Unfiltered signal
2. 13
DIA5 function
1:
External fault, closing contact = Fault is shown and motor is stopped when
the input is active
2:
External fault, opening contact = Fault is shown and motor is stopped when
the input is not active
3:
Run enable
contact open
= Start of the motor disabled
contact closed
= Start of the motor enabled
4:
Acc. / Dec
contact open
= Acceleration/Deceleration time 1 selected
time select.
contact closed
= Acceleration/Deceleration time 2 selected
5:
Reverse
contact open
= Forward
If two or more inputs are
contact closed
= Reverse
programmed to reverse then
if one of them is active the
direction is reverse
6:
Jogging freq.
contact closed
= Jogging frequency selected for freq. refer.
7:
Fault reset
contact closed
= Resets all faults
8:
Acc./Dec.
contact closed
= Stops acceleration and deceleration until
operation
the contact is opened
prohibited
9:
DC-braking
contact closed
= In the stop mode, the DC-braking operates
command
until the contact is opened, see figure 6-1.
DC-brake current is set with parameter 4
.
8.
10:
PI-contr. ref.
contact closed
= reference 2 (selected with par. 2.29) is
selection
active
11:
Interlock inp. contact closed = Interlock of autochange drive 3 is active
autochange 3
2. 14
Motor potentiometer ramp time
Defines how fast the electronic motor potentiometer value changes.