Pump control with autochange
Code
Parameter
Range
Step
Default
Custom
Description
Page
2
.
14
Motor potentiometer
0.1—2000.0
0.1
10.0
22
ramp time
Hz/s
Hz/s
Hz/s
2
.
15
PI-controller reference
0—6
1
2
0
= U
in
signal (control board)
22
signal (source A)
1= I
in
signal (control board)
2 = Set reference from the panel
(reference r2)
3 = Signal from internal motor pot.
4 = Signal from internal motor pot.
reset if Vacon unit is stopped
5 = Option board Ain1-signal
6 = Option board Ain2-signal
7 = Fieldbus signal
2
.
16
PI-controller actual
0—7
1
0
0 = Actual value1
23
value selection
1 = Actual 1 + Actual 2
2 = Actual 1 - Actual 2
3 = Actual 1 * Actual 2
4 = MIN(Actual1, Actual2)
5 = MAX(Actual1, Actual2)
6 = MEAN(Actual1, Actual2)
7 = SQRT(Act1) + SQRT(Act2)
2
.
17
Actual value 1 input
0—4
1
2
0 = No
23
1 = U
in
signal (control board)
2 = I
in
signal (control board)
3 = Option board Ain1-signal
4 = Option board Ain2-signal
5 = Fieldbus signal
2
.
18
Actual value 2 input
0—4
1
0
0 = No
23
1 = U
in
signal (control board)
2 = I
in
signal (control board)
3 = Option board Ain1-signal
4 = Option board Ain2-signal
2
.
19
Actual value 1
-320.00%—
0.01%
0%
0% = no minimum scaling
23
min scale
+320.00%
2
.
20
Actual value 1
-320.00%—
0.01%
100%
100% = no maximum scaling
23
max scale
+320.00%
2
.
21
Actual value 2
-320.00%—
0.01%
0%
0% = no minimum scaling
23
min scale
+320.00%
2
.
22
Actual value 2
-320.00%—
0.01%
100%
100% = no maximum scaling
23
max scale
+320.00%
2
.
23
Error value inversion
0—1
1
0
0 = No
24
1 = Yes
2
.
24
PI-controller reference
0—100.0 s
0.1 s
5 s
Time for reference value change
24
value rise time
from 0 % to 100 %
2
.
25
PI-controller reference
0—100.0 s
0.1 s
5 s
Time for reference value change
24
value fall time
from 100 % to 0 %
Note!
= Parameter value can be changed only when the frequency converter is stopped (Continues)