Page 17
Pump control with autochange
Code
Parameter
Range
Step
Default
Custom
Description
Page
7
.
10
Stall protection
0—2
1
1
0 = No action
39
1 = Warning
2 = Fault
7
.
11
Stall current limit
10.0—200%
1.0%
130.0%
40
x I
nMOTOR
7
.
12
Stall time
2.0—120 s
1.0 s
15.0 s
40
7
.
13
Maximum stall frequency
1—f
max
1 Hz
25 Hz
40
7
.
14
Underload protection
0—2
1
0
0 = No action
41
1 = Warning
2 = Fault
7
.
15
Underload prot., field
20.0—150 %
1.0%
50.0%
41
weakening area load
x T
nMOTOR
7
.
16
Underload protection,
10.0—150.0%
1.0%
10.0%
41
zero frequency load
x T
nMOTOR
7
.
17
Underload time
2.0—600.0 s
1.0 s
20.0s
41
7. 18
Phase supervision of
0—2
2
2
0 = No action
42
the supply voltage
2 = Fault
7
.
19
Termistor input of
0—2
1
2
0 = No action
42
I/O-Expander
1 = Warning
2 = Fault
7.20 Fieldbus fault
0 - 2
1
2
0 = No action
1= Warning
2 = Fault
Group 8, Autorestart parameters
Code
Parameter
Range
Step Default Custom
Description
Page
8
.
1
Automatic restart:
0—10
1
2
0 = Not used
42
number of tries
8
.
2
Automatic restart:
1—6000 s
1 s
30 s
42
trial time
8
.
3
Automatic restart:
0—1
1
0
0 = Ramp
43
start function
1 = Flying start
8
.
4
Automatic restart after
0—1
1
1
0 = No
43
undervoltage trip
1 = Yes
8
.
5
Automatic restart after
0—1
1
1
0 = No
43
overvoltage trip
1 = Yes
8
.
6
Automatic restart after
0—1
1
1
0 = No
43
overcurrent trip
1 = Yes
8
.
7
Automatic restart after
0—1
1
1
0 = No
43
reference fault trip
1 = Yes
8
.
8
Automatic restart after
0—1
1
1
0 = No
43
over/undertemperature
1 = Yes
fault trip