Pump and fan control with autochange
Terminal
Signal
Description
301
DID1
External fault
Contact open = no fault
(closing contact)
Contact closed = fault
302
DID2
RUN disable
Contact open=start of motor enable
Contact closed=start of motor
disabled
303
DID3
Acceler. / Decel. time
Contact open = time 1 selected
selection
Contact closed = time 2 selected
304
DID4
Jogging speed selection
Contact open = no action
Contact closed = jogging speed
305
COMD
Common for DID1-DID2
Connect to GND or +24 V
306
+24 V
Control voltage output
Voltage for switches, etc. max. 0.1 A
307
COME
Common for DIE3-DIE4
Connect to GND or +24 V
308
GND
I/O ground
Ground for reference and controls
309
DID5A+ Pulse input A
310
DID5A-
(differential input)
311
DID6B+ Pulse input B
90 degrees phase shift compared
312
DID6B-
(differential input)
to pulse input A
313
DID7Z+ Pulse input Z
one pulse per one revolution
314
DID7Z-
(differential input)
315
GND
I/O ground
Ground for reference and controls
316
DOD1
Open collector output 1
Aux. drive 1 / autochange 1 control
317
DOD2
Open collector output 2
Aux. drive 2 / autochange 2 control
318
DOD3
Open collector output 3
Aux. drive 3 / autochange 3 control
319
DOD4
Open collector output 4
Fieldbus control
320
GND
I/O ground
Ground for reference and controls
327
TI+
Termistor input
328
TI-
Figure 7-5 I/O-Expander 200OPT with pump and fan control (Interbus-S)
Signal from
motor termistor