Pump control with autochange
Group 3, Output and supervision parameters
Code
Parameter
Range
Step
Default
Custom
Description
Page
3
.
1
Analogue output function
0—15
1
1
0 = Not used
Scale 100%
26
1 = O/P frequency
(0—f
max
)
2 = Motor speed
(0—max. speed)
3 = O/P current
(0—2.0 x I
nCX
)
4 = Motor torque
(0—2 x T
nCX
)
5 = Motor power
(0—2 x P
nCX
)
6 = Motor voltage
(0—100% xU
nM
)
7 = DC-link volt.
(0—1000 V)
8—10 = Not in use
11 = PI-controller reference value
12 = PI-controller actual value 1
13 = PI-controller actual value 2
14 = PI-controller error value
15 = PI-controller output
3
.
2
Analogue output filter time
0.01—10 s
0.01
1.00
26
3
.
3
Analogue output inversion
0—1
1
0
0 = Not inverted
26
1 = Inverted
3
.
4
Analogue output minimum
0—1
1
0
0 = 0 mA
26
1 = 4 mA
3
.
5
Analogue output scale
10—1000%
1%
100%
26
3
.
6
Digital output function
0—30
1
3
0 = Not used
27
1 = Ready
2 = Run
3 = Fault
4 = Fault inverted
5 = Vacon overheat warning
6 = External fault or warning
7 = Reference fault or warning
8 = Warning
9 = Reversed
10 = Jogging speed selected
11 = At speed
12 = Motor regulator activated
13 = Output freq. limit superv. 1
14 = Output freq. limit superv. 2
15 = Torque limit supervision
16 = Reference limit supervision
17 = External brake control
18 = Control from I/O terminals
19 = Frequency converter
temperature limit supervision
20 = Unrequested rotation direction
21 = External brake control inverted
22 = Analogue input supervision
22—26 = Not in use
27 =Autochange 3 control
28 = Auxiliary drive 1 start
29 = Auxiliary drive 2 start
30 = Auxiliary drive 3 start
3
.
7
Relay output 1 function
0—31
1
26
0-25 = As parameter 3
.
6
27
26 = Autochange 1 control
27 = Autochange 4 control
28-30 = As parameter 3
.
6
31 = Aux. drive 4 start
3
.
8
Relay output 2 function
0—30
1
26
0-25 = As parameter 3
.
6
28
26 = Autochange 2 control
27 = Autochange 5 control
28-30 = As parameter 3
.
6
Note!
= Parameter value can be changed only when the frequency converter is stopped. (Continues)