Vacon
Pump and fan control with autochange
Note!
=Parameter value can be changed only when the frequency converter is stopped.
(Continues)
Group 9, Pump and fan control special parameters
Code
Parameter
Range
Stepl
Default
Custom
Description
Page
9
.
1
Number of aux. drives
0—4
1
1
44
9
.
2
Start frequency of
f
min
—
0.1 Hz 51.0 Hz
starting
44
auxiliary drive 1
120/500
9
.
3
Stop frequency of
f
min
—
0.1 Hz 10.0 Hz
stopping
44
auxiliary drive 1
Par. 9.2
9
.
4
Start frequency of
f
min
—
0.1 Hz 51.0 Hz
starting
44
auxiliary drive 2
120/500
9
.
5
Stop frequency of
f
min
—
0.1 Hz 10.0 Hz
stopping
44
auxiliary drive 2
Par. 9.4
9
.
6
Start frequency of
f
min
—
0.1 Hz
51.0 Hz
starting
44
auxiliary drive 3
120/500
9
.
7
Stop frequency of
f
min
—
0.1 Hz
10.0 Hz
stopping
44
auxiliary drive 3
Par. 9.6
9
.
8
Start frequency of
f
min
—
0.1 Hz 51.0 Hz
Needs I/O-expander option board
44
auxiliary drive 4
120/500
9
.
9
Stop frequency of f
min
— 0.1 Hz 10.0 Hz
Needs I/O-expander option board 44
auxiliary drive 4 Par. 9.8
9
.
10
Start delay of the
0—300.0 s
0.1 s
4.0 s
44
auxiliary drives
9
.
11
Stop delay of the
0—300.0 s
0.1 s
2.0 s
44
auxiliary drives
9
.
12
Reference step after
0—100.0 %
0.1 %
0.0 %
In % of actual value
45
start of the 1 aux. drive
9
.
13
Reference step after
0—100.0 %
0.1 %
0.0 %
In % of actual value
45
start of the 2 aux. drive
9
.
14
Reference step after
0—100.0 %
0.1 %
0.0 %
In % of actual value
45
start of the 3 aux. drive
9
.
15
Reference step after
0—100.0 %
0.1 %
0.0 %
In % of actual value
45
start of the 4 aux. drive
9
.
16
Sleep level
0—120/500
0.1 Hz 10.0 Hz
Frequency below which the freq.
46
Hz
of the speed controlled motor has
go before starting the sleep delay
counting ( 0.0 = not in use)
9
.
17
Sleep delay
0—3000.0 s
0.1 s
30.0 s
Time that the freq. has to be below
46
par. 9
.
16 before stopping Vacon
9
.
18
Wake up level
0—100.0 %
0.1 %
25.0 %
Level of the actual value for
46
restarting Vacon
9
.
19
Wake up function
0—3
1
0
0 = Wake up falling below the level
46
Level % from actual max. value
1 = Wake up exceeding the level
Level % from actual max. value
2 = Wake up falling below the level
Level % from current reference
3 = Wake up exceeding the level
Level % from current reference