Pump and fan control with autochange
Code
Parameter
Range
Step
Default
Custom
Description
Page
3
.
9
Output freq. limit 1
0—2
1
0
0 = No
28
supervision function
1 = Low limit
2 = High limit
3
.
10
Output freq. limit 1
0—f
max
0.1 Hz
0 Hz
28
supervision value
(par. 1
.
2)
3
.
11
Output freq. limit 2
0—2
1
0
0 = No
28
supervision function
1 = Low limit
2 = High limit
3
.
12
Output freq. limit 2
0—f
max
0.1 Hz
0 Hz
28
supervision value
(par. 1
.
2)
3
.
13
Torque limit
0—2
1
0
0 = No
28
supervision function
1 = Low limit
2 = High limit
3
.
14
Torque limit
0—200% x
1%
100%
28
supervision value
T
nCX
3
.
15
Active reference limit
0—2
1
0
0 = No
29
supervision function
1 = Low limit
2 = High limit
3
.
16
Active reference limit
0—f
max
0.1 Hz
0 Hz
29
supervision value
(par. 1
.
2)
3
.
17
External brake off-delay
0—100.0 s
1
0.5 s
29
3
.
18
External brake on-delay
0—100.0 s
1
0.5 s
29
3
.
19
Frequency converter
0—2
1
0
0 = No
30
temperature limit
1 = Low limit
supervision function
2 = High limit
3
.
20
Frequency converter
-10—+75°C
1
+40°C
30
temperature limit
3
.
21
I/O-expander board (opt.)
0—7
1
3
See parameter 3
.
1
30
analogue output content
3
.
22
I/O-expander board (opt.)
0.01—10 s
0.01
1.00
See parameter 3
.
2
30
analogue output filter time
3
.
23
I/O-expander board (opt.)
0—1
1
0
See parameter 3
.
3
30
analogue output inversion
3
.
24
I/O-expander board (opt.)
0—1
1
0
See parameter 3
.
4
30
analogue output minimum
3
.
25
I/O-expander board (opt.) 10—1000%
1
100%
See parameter 3
.
5
30
analogue output scale
3. 26
Analog output bias
0—100,00%
0,01%
0,00%
30
(basic control board)
3. 27
I/O-expander board (opt.) 0—100,00%
0,01%
0,00%
30
analogue output bias
3
.
28
Analogue input
0—2
1
0
0 = U
in
signal (control board)
30
supervision input
1 = I
in
signal (control board)
2 = Option board Ain1-signal
3 = Option board Ain2-signal
3
.
29
Analogue input
0—2
1
0
0 = No
30
supervision function
1 = Low limit
2 = High limit
3
.
30
Analogue input
0—100%
0.1 %
0,0 %
30
supervision value