Vacon Plc
Phone: +358-201 2121
Fax:+358-201 212 205
Service: +358-40-8371 150
E-mail: [email protected]
E-mail: [email protected]
Vacon
Page 15
Pump control with autochange
Group 4, Drive control parameters
Code
Parameter
Range
Step
Default
Custom
Description
Page
4
.
1
Acc./dec. ramp 1 shape
0—10 s
0.1 s
0
0 = Linear
31
>0 = S-curve acc./dec. time
4
.
2
Acc./dec. ramp 2 shape
0—10 s
0.1 s
0
0 = Linear
31
>0 = S-curve acc./dec. time
4
.
3
Acceleration time 2
0.1—3000 s
0.1 s
10 s
31
4
.
4
Deceleration time 2
0.1—3000 s
0.1 s
10 s
31
4
.
5
Brake chopper
0—1
1
0
0 = Brake chopper not in use
31
1 = Brake chopper in use
2 = External brake chopper
4
.
6
Start function
0—1
1
0
0 = Ramp
32
1 = Flying start
4
.
7
Stop function
0—1
1
0
0 = Coasting
32
1 = Ramp
4
.
8
DC-braking current
0.15—1.5 x
0.1 A
0.5 x
32
I
nCX
(A)
I
nCX
4
.
9
DC-braking time at Stop
0—250.00 s
0.01 s
0 s
0 = DC-brake is off at Stop
33
4
.
10
Execute frequency of DC-
0.1 Hz
1.5 Hz
34
brake during ramp stop
4
.
11
DC-brake time at Start
0—250.00 s
0.01 s
0 s
0 = DC-brake is off at Start
34
4
.
12
Jogging speed reference
f
min
—f
max
0.1 Hz 10.0 Hz
34
(1
.
1) (1
.
2)
Group 5, Prohibit frequency parameters
Code
Parameter
Range
Step
Default
Custom
Description
Page
5
.
1
Prohibit frequency
0—f
max
0.1 Hz
0 Hz
34
range 1 low limit
(1
.
2)
5
.
2
Prohibit frequency
0—f
max
0.1 Hz
0 Hz
0 = No prohibit frequency range
34
range 2 high limit
(1
.
2)
5
.
3
Prohibit frequency
0—f
max
0.1 Hz
0 Hz
34
range 2 low limit
(1
.
2)
5
.
4
Prohibit frequency
0—f
max
0.1 Hz
0 Hz
0 = No prohibit frequency range
34
range 2 high limit
(1
.
2)
5
.
5
Prohibit frequency
0—f
max
0.1 Hz
0 Hz
34
range 3 low limit
(1
.
2)
5
.
6
Prohibit frequency
0—f
max
0.1 Hz
0 Hz
0 = No prohibit frequency range
34
range 3 high limit
(1
.
2)
Note!
= Parameter value can be changed only when the frequency converter is stopped. (Continues)