128
107672-01 - 7/17
XII. Operation
F. Changing Adjustable Parameters (continued)
“Press”
button to access the following parameters:
Factory
Setting
Range / Choices
Parameter and Description
Enabled
Enable Disable
Auxiliary Heat Outdoor Reset Enable
If an outdoor sensor is installed and Outdoor Reset is Enabled, the boiler will automatically
adjust the heating zone set point temperature based on the outdoor reset curve in Figure
8. The maximum set point is defined by the Central Heat Setpoint [factory set to 180°F
(82.2°C)] when the outdoor temperature is 0°F (-18°C) or below. The minimum set point
temperature shown is 130°F (54.4°C) [adjustable as low as 80°F (26.7°C)] when the
outdoor temperature is 50°F (10°C) or above. As the outdoor temperature falls the supply
water target temperature increases. For example, if the outdoor air temperature is 30°F,
(-1.1°C) the set point temperature for the supply water is 150°F (65.6°C).
Disable
Do Not
Calculate setpoint based on outdoor temperature
Enable
Calculate the temperature setpoint based on outdoor temperature using a reset
curve defined by Low Outdoor Temp, High Outdoor Temp, Low Boiler Water
Temp, Min Boiler Temp and Central Heat Setpoint and Boost Time parameters.
0°F
(-18°C)
-40°F to 100°F
(-40°C to 37.8°C)
Auxiliary Heat Low Outdoor Temperature
The Low Outdoor Temperature parameter is also called “Outdoor Design Temperature”.
This parameter is the outdoor temperature used in the heat loss calculation. It is typically
set to the coldest outdoor temperature.
70°F
(21.1°C)
32°F to 100°F
(0°C to 37.8°C)
Auxiliary Heat High Outdoor Temperature
The High Outdoor Temperature parameter is the outdoor temperature at which the Low
Boiler Water Temperature is supplied. This parameter is typically set to the desired building
temperature.
110°F
(43.3°C)
70°F to 190°F
(21.1°C to 87.8°C)
Auxiliary Heat Low Boiler Water Temperature
The Low Boiler Water Temperature parameter is the operating setpoint when the High
Outdoor Temperature is measured. If the home feels cool during warm outdoor conditions,
the Low Boiler Water Temperature parameter should be increased.
20 Minutes
0-1800 Seconds
(0-30 Minutes)
Auxiliary Heat Boost Time
When the Auxiliary Heat Setpoint is decreased by Outdoor Reset settings, the Boost Time
parameter is used to increase the operating setpoint when the home heat demand is not
satisfied after the Boost Time setting is exceeded. When heat demand has been “on”
continuously for longer than the Boost Time parameter the operating setpoint is increased
by 10°F (5.6°C). The highest operating setpoint from Boost Time is current Auxiliary Heat
Setpoint. A setting of 0 seconds disables this feature.
Содержание K2WT-080B
Страница 11: ...11 107672 01 7 17 Figure 5 1 Wall Layout Mounting Hole Location V Mounting The Boiler continued...
Страница 79: ...79 107672 01 7 17 Figure 9 6 Piping Method 1 Near Boiler Piping Shaded Boiler Loop IX System Piping continued...
Страница 83: ...83 107672 01 7 17 PAGE LEFT INTENTIONALLY BLANK...
Страница 89: ...89 107672 01 7 17 X Wiring continued Figure 10 5 Internal Ladder Diagram...
Страница 90: ...90 107672 01 7 17 X Wiring continued...
Страница 91: ...91 107672 01 7 17 Figure 10 6 Internal Wiring Connections Diagram X Wiring continued...
Страница 93: ...93 107672 01 7 17 Figure 10 8 TACO SR504 or Equivalent Zone Panel Wiring Connection Diagram X Wiring continued...
Страница 94: ...94 107672 01 7 17 X Wiring continued Figure 10 9 Sage Zone Control Circulator Panel Wiring Connection Diagram...
Страница 102: ...102 107672 01 7 17 Lighting and Operating Instructions XI Start Up and Checkout continued...
Страница 147: ...147 107672 01 7 17 XV Service Parts continued...
Страница 151: ...151 107672 01 7 17 XV Service Parts continued...
Страница 153: ...153 107672 01 7 17 XV Service Parts continued 85 86 91 95...
Страница 162: ...162 107672 01 7 17...
Страница 163: ...163 107672 01 7 17...
Страница 164: ...164 107672 01 7 17...
Страница 165: ...165 107672 01 7 17...
Страница 166: ...166 107672 01 7 17...
Страница 167: ...167 107672 01 7 17...
Страница 168: ...168 107672 01 7 17 U S Boiler Company Inc P O Box 3020 Lancaster PA 17604 1 888 432 8887 www usboiler net...