1
Opening for reset button
Reset button on the system control
Fig. 7-15
5. Insert a small pen tip or piece of wire into the opening for
the Reset button and press and hold down the Reset button
for 3 seconds.
6. Switch 24 V supply voltage off and back on again to restart
the system.
The IP address of the TruConvert System Control is reset
to: 192.168.1.2
7. To change the network settings:
−
User interface:
Enter new values for "IP Subnet Mask", "IP Host" and
"IP Gateway".
Press "Submit IP Configuration".
−
Modbus:
Enter new values for IP subnet and IP gateway
.
The network settings are transferred to the system control.
A67-0140-00.BKen-0
01-05
2020-07-01
System control
7
‐
33
Changing the IP subnet and
gateway