or
■
If it is not possible to fully discharge the battery, appropriate
separators are to be installed in the connection between DC-
DC module and battery.
■
The separation devices must comply with applicable stand-
ards.
■
Before closing the separators, the battery connections must
be pre-charged to the current battery voltage!
Means, Tools, Materials
■
Terminating resistor for the data output (provided).
■
Ferrite core for 24 V supply cable (provided).
■
If necessary, pre-charger for pre-charging the battery connec-
tions on the DC-DC module to battery voltage.
Note
To ensure safe operation,
both
protective earth connections
must be connected to the earthing system with
2 separate
PE conductors.
1. Screw protective earth to the internal thread of the housing
back panel. Max. torque: 8 Nm.
2. Screw protective earth to the threaded bolt on the cover
hood. Max. torque: 8 Nm.
3. Screw protective earth on TruConvert System Control. Max.
torque: 2 Nm.
4. Fully discharge the battery and ensure absence of voltage.
or
Ø
If the battery cannot be discharged: open separators on
the battery.
5. Remove the cover for the battery connection on the DC-DC
module.
6. Ensure that the end sleeves of the battery cables are insu-
lated with suitable shrink tubing.
7. Connect the battery cables. Observe polarity. Max. torque:
25 Nm.
8. Screw the cover for battery connections back on. Max. tor-
que: 2 Nm.
9. When working with charged battery, also perform the follow-
ing steps:
−
Ensure that the separator is open.
−
Pre-charge battery connections to current battery voltage
with suitable pre-charger.
−
Close separator.
A67-0140-00.BKen-0
01-05
2020-07-01
Electrical connection
6
‐
9
Connecting protective earth
to DC-DC module
Connecting protective earth
to system control
Connecting the battery
Содержание TruConvert DC 1000 Series
Страница 1: ...Operator s manual TruConvert DC series 1000 TruConvert System Control TruConvert Modular...
Страница 2: ......
Страница 6: ...II Good to know 2020 07 01 A67 0140 00 BKen 0 01 05...
Страница 36: ...3 12 Technical data dependent on device variant overview 2020 07 01 A67 0140 00 BKen 0 01 05...
Страница 38: ...7 Ethernet 4 10 8 RS 485 4 11 4 2 Interfaces 2020 07 01 A67 0140 00 BKen 0 01 05...
Страница 40: ...Fig 4 3 4 4 Protective earth TruConvert DC series 1000 2020 07 01 A67 0140 00 BKen 0 01 05...
Страница 48: ...4 12 RS 485 2020 07 01 A67 0140 00 BKen 0 01 05...
Страница 54: ...5 6 CSA certification 2020 07 01 A67 0140 00 BKen 0 01 05...
Страница 106: ...16 State diagram State machine Fig 7 19 7 38 State diagram 2020 07 01 A67 0140 00 BKen 0 01 05...