Requirements for the site
Operation is permissible indoors only.
Sufficient space must be present for air intake and air outlet.
1
Minimum distance for air out-
let: 300 mm
2
Fan
3
Minimum distance for air
intake: 200 mm
Air circulation intervals
Fig. 6-1
Sufficient cooling of the module is only ensured if a sufficient air
flow rate up to a maximum permissible back pressure is pro-
vided.
In addition, note that the air flow rate must be multiplied by the
number of devices if several modules are operated.
Air short circuits and mutual interference of the modules must
be prevented.
Number of modules
Air flow rate
Maximum back pres-
sure in the air duct
1
200 m³/h
20 Pa
n
n x 200 m³/h
20 Pa
Maximum back pressure
Tab. 6-1
Access to the external mains separation device must not be
obstructed by the device.
Fuses must be provided on-site by the customer .
6
‐
6
Requirements for the site
2020-07-01
A67-0140-00.BKen-0
01-05
Installation indoors
Air intake and air outlet
Maximum back pressure
Mains separation device
Fuses
Содержание TruConvert DC 1000 Series
Страница 1: ...Operator s manual TruConvert DC series 1000 TruConvert System Control TruConvert Modular...
Страница 2: ......
Страница 6: ...II Good to know 2020 07 01 A67 0140 00 BKen 0 01 05...
Страница 36: ...3 12 Technical data dependent on device variant overview 2020 07 01 A67 0140 00 BKen 0 01 05...
Страница 38: ...7 Ethernet 4 10 8 RS 485 4 11 4 2 Interfaces 2020 07 01 A67 0140 00 BKen 0 01 05...
Страница 40: ...Fig 4 3 4 4 Protective earth TruConvert DC series 1000 2020 07 01 A67 0140 00 BKen 0 01 05...
Страница 48: ...4 12 RS 485 2020 07 01 A67 0140 00 BKen 0 01 05...
Страница 54: ...5 6 CSA certification 2020 07 01 A67 0140 00 BKen 0 01 05...
Страница 106: ...16 State diagram State machine Fig 7 19 7 38 State diagram 2020 07 01 A67 0140 00 BKen 0 01 05...